ELE06-00313
| ELE-Aging Inspection | 6/12/2007 | 6/12/2007 | 6/13/2007 6:27:22 AM | | NR |
|
|
drove by job site still under construction
|
ELE07-02109
| Final | 6/12/2007 | 6/12/2007 | 6/12/2007 5:24:24 PM | P | PASS |
|
|
ok final
|
ELE07-02109
| Electrical Rough-In | 6/11/2007 | 6/12/2007 | 6/12/2007 5:23:54 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer ok ri
|
ELE07-02122
| Temporary Service | 6/12/2007 | 6/12/2007 | 6/12/2007 5:23:27 PM | P | PASS |
|
|
glenn ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith t/s o/h n ok
|
ELE07-01921
| Conference | 6/12/2007 | 6/12/2007 | 6/12/2007 3:35:03 PM | P | PASS |
|
|
Shawn - Mike this is for a uffer ground; Phone #: ###-#### Internet Inspection Request from: Darla Downs conf they can connect grounding electrode to exessing rebar in the foundation or they can clean the tar off footing foundation & pour 2inch or more concrete over it
|
ELE07-02117
| Electrical Rough-In | 6/12/2007 | 6/12/2007 | 6/12/2007 3:32:00 PM | P | NR |
|
|
Shawn - Mike please if possible make this the last inspection ; Phone #: ###-#### Internet Inspection Request from: Darla Downs job not ready
|
ELE07-02119
| Electrical Rough-In | 6/12/2007 | 6/12/2007 | 6/12/2007 3:31:13 PM | P | PASS |
|
|
greg; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang ok cover ri
|
ELE07-02117
| Conference | 6/12/2007 | 6/12/2007 | 6/12/2007 2:23:10 PM | P | PASS |
|
|
Shawn - Mike this is for a uffer ground; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok to connect to rebar in foundation or clean tar away from footing & foundation
|
ELE07-02001
| Electrical Rough-In | 6/12/2007 | 6/12/2007 | 6/12/2007 1:20:16 PM | P | FAIL |
|
|
Rough-in, approval for cover inspection. Phone #: ###-#### Internet Inspection Request from: Kathy Briggs correction nec300.4(D) 1 1/4 from edge of framing members through out the area
|
ELE07-00272
| Permanent Service | 6/11/2007 | 6/12/2007 | 6/12/2007 11:06:27 AM | A | NR |
|
|
Service inspect call Steve Ruter Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson conf with electrician
|
ELE07-02102
| Final | 6/12/2007 | 6/12/2007 | 6/12/2007 10:21:36 AM | A | PASS |
|
|
ok final
|
ELE07-02102
| Electrical Rough-In | 6/11/2007 | 6/12/2007 | 6/12/2007 10:20:44 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer ok cover ri
|
ELE07-01200
| Final | 6/11/2007 | 6/12/2007 | 6/12/2007 8:37:35 AM | A | PASS |
|
|
Final inspection of a clean room tool installed in building 15. Phone #: ###-#### Internet Inspection Request from: Del Elwood ok final
|
ELE06-02969
| Final | 6/12/2007 | 6/12/2007 | 6/12/2007 7:22:22 AM | A | PASS |
|
|
ok final
|
ELE06-02969
| ELE-Aging Inspection | 6/12/2007 | 6/12/2007 | 6/12/2007 7:21:31 AM | | PASS |
|
|
ok final
|