FIR08-00374
| INSP-Final Inspection | 6/11/2008 | 6/12/2008 | 6/13/2008 4:47:40 PM | P | PASS |
|
|
Fire alarm system modifications passed field test, one faulty appliance replaced and retested while on site, permit finaled.
|
FIR08-00296
| INSP-Final Inspection | 6/11/2008 | 6/12/2008 | 6/13/2008 4:46:20 PM | P | PASS |
|
|
Fire alarm testing passed, permit finaled.
|
FIR07-00663
| INSP-Sprinkler Rough-in/Hydro | 6/12/2008 | 6/12/2008 | 6/12/2008 3:55:28 PM | P | PART |
|
|
Final pending system fire alarm interconnection.
|
BLD08-01124
| FIRE-Final Inspection | 6/12/2008 | 6/12/2008 | 6/12/2008 3:34:43 PM | P | PASS |
|
|
Fire life safety finaled, tenant remodel inspection passed.
|
FIR08-00409
| INSP-Final Inspection | 6/12/2008 | 6/12/2008 | 6/12/2008 3:33:40 PM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR08-00409
| INSP-Sprinkler Rough-in | 6/12/2008 | 6/12/2008 | 6/12/2008 3:33:10 PM | P | PART |
|
|
OH fire sprinkler system modifications are acceptable.
|
FIR08-00045
| INSP-Sprinkler Rough-in/Hydro | 6/12/2008 | 6/12/2008 | 6/12/2008 2:10:05 PM | P | NR |
|
|
Jerry Phone#: ###-####
|
FIR07-00935
| INSP-Sprinkler Rough-in/Hydro | 6/12/2008 | 6/12/2008 | 6/12/2008 2:09:35 PM | P | PART |
|
|
OH hydrostatic testing for both wet systems passed. OH rough-in failed due to overspaced heads at the wash bay, blocked heads at the compressor room, missing EQ brace at the 4" main NE corner of the warehouse, need to provide resubmittals for pipe size changes at the north office areas, some finish items at the riser are not complete including flex. couplings, FDC ball drip, head box, tagged DCVA, etc.
|
FIR07-00273
| FIR-Aging Inspection | 6/12/2008 | 6/12/2008 | 6/12/2008 12:22:31 PM | A | PEND |
|
|
Pending final inspection for work completed.
|
FIR07-00905
| INSP-Final Inspection | 6/12/2008 | 6/12/2008 | 6/12/2008 12:21:28 PM | A | PART |
|
|
Permit final pending supply line flush.
|
BLD07-00855
| FIRE-Final Inspection | 6/11/2008 | 6/12/2008 | 6/12/2008 12:18:49 PM | A | PASS |
|
|
Correction notice items verified for compliance, shell life safety finaled.
|
FIR07-00691
| INSP-Final Inspection | 6/11/2008 | 6/12/2008 | 6/12/2008 12:17:54 PM | A | PASS |
|
|
Fire sprinkler work passed field inspection, permit finaled.
|