Inspections for the day of: Tuesday, June 12, 2012.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD12-00617 FIRE-Final Inspection6/11/20126/12/20126/12/2012 3:51:45 PMPFAIL
Life safety passed for the "vanilla finish". Owner wanted an actual occupancy so per onsite agreement I'm failing this inspection until the owner revises the submittal application for an occupancy permit and sets up a re-inspection.
FIR12-00185 INSP-Sprinkler Rough-in6/12/20126/12/20126/12/2012 3:39:08 PMPFAIL
Three pendant sprinkler heads are located too far off of a south wall which gives them an overall spacing of 140 sq. ft. per head. 130 sq. ft. per head is maximum. Also I need as-builts due to an existing line shown as 1 1/2" but is actually 3" in size. I did give Max, the project superintendant, permission to cover. I will verify the three relocated heads at the final.
FIR12-00161 INSP-Final Inspection6/11/20126/12/20126/12/2012 3:34:19 PMPCANC
Canceled per onsite conversation with the project superintendant for Inland Construction. Touch-up work is not yet complete and heads are still covered and missing cover plates.
BLD11-01267 FIRE-Alarm Testing6/12/20126/12/20126/12/2012 3:06:11 PMPDONE
For todays inspection I finished testing the residence room smoke alarms in the first floor north section up to the fire wall.
BLD12-01109 FIRE-Final Inspection6/12/20126/12/20126/12/2012 12:57:49 PMPPASS
life safety passed
FIR11-00543 INSP-Sprinkler Rough-in/Hydro6/11/20126/12/20126/12/2012 12:36:19 PMACANC
Cancel per phone conversation with Scott Carter
BLD12-00248 FIRE-Final Inspection6/12/20126/12/20126/12/2012 10:09:32 AMPPART
Temporary occupancy is ok per Scott and Romeo for the employee use only. Business is not to be opened to the public. The interior emergency lighting is the last item needing to be addressed.
FIR12-00249 INSP-Final Inspection6/12/20126/12/20126/12/2012 9:45:06 AMPPASS
Permit finaled
BLD12-00981 FIRE-Alarm Testing6/11/20126/12/20126/12/2012 9:32:04 AMPPASS
Life safety passed
FIR12-00259 INSP-Final Inspection6/11/20126/12/20126/12/2012 9:31:38 AMAPASS
Permit finaled
BLD12-00956 FIRE-Final Inspection6/11/20126/12/20126/12/2012 9:30:34 AMAPASS
Life safety passed.
FIR12-00258 INSP-Final Inspection6/11/20126/12/20126/12/2012 9:30:07 AMAPASS
Permit finaled
FIR12-00281 INSP-Final Inspection6/11/20126/12/20126/12/2012 8:21:38 AMAPASS
Permit finaled