BLD12-00617
| FIRE-Final Inspection | 6/11/2012 | 6/12/2012 | 6/12/2012 3:51:45 PM | P | FAIL |
|
|
Life safety passed for the "vanilla finish". Owner wanted an actual occupancy so per onsite agreement I'm failing this inspection until the owner revises the submittal application for an occupancy permit and sets up a re-inspection.
|
FIR12-00185
| INSP-Sprinkler Rough-in | 6/12/2012 | 6/12/2012 | 6/12/2012 3:39:08 PM | P | FAIL |
|
|
Three pendant sprinkler heads are located too far off of a south wall which gives them an overall spacing of 140 sq. ft. per head. 130 sq. ft. per head is maximum. Also I need as-builts due to an existing line shown as 1 1/2" but is actually 3" in size. I did give Max, the project superintendant, permission to cover. I will verify the three relocated heads at the final.
|
FIR12-00161
| INSP-Final Inspection | 6/11/2012 | 6/12/2012 | 6/12/2012 3:34:19 PM | P | CANC |
|
|
Canceled per onsite conversation with the project superintendant for Inland Construction. Touch-up work is not yet complete and heads are still covered and missing cover plates.
|
BLD11-01267
| FIRE-Alarm Testing | 6/12/2012 | 6/12/2012 | 6/12/2012 3:06:11 PM | P | DONE |
|
|
For todays inspection I finished testing the residence room smoke alarms in the first floor north section up to the fire wall.
|
BLD12-01109
| FIRE-Final Inspection | 6/12/2012 | 6/12/2012 | 6/12/2012 12:57:49 PM | P | PASS |
|
|
life safety passed
|
FIR11-00543
| INSP-Sprinkler Rough-in/Hydro | 6/11/2012 | 6/12/2012 | 6/12/2012 12:36:19 PM | A | CANC |
|
|
Cancel per phone conversation with Scott Carter
|
BLD12-00248
| FIRE-Final Inspection | 6/12/2012 | 6/12/2012 | 6/12/2012 10:09:32 AM | P | PART |
|
|
Temporary occupancy is ok per Scott and Romeo for the employee use only. Business is not to be opened to the public. The interior emergency lighting is the last item needing to be addressed.
|
FIR12-00249
| INSP-Final Inspection | 6/12/2012 | 6/12/2012 | 6/12/2012 9:45:06 AM | P | PASS |
|
|
Permit finaled
|
BLD12-00981
| FIRE-Alarm Testing | 6/11/2012 | 6/12/2012 | 6/12/2012 9:32:04 AM | P | PASS |
|
|
Life safety passed
|
FIR12-00259
| INSP-Final Inspection | 6/11/2012 | 6/12/2012 | 6/12/2012 9:31:38 AM | A | PASS |
|
|
Permit finaled
|
BLD12-00956
| FIRE-Final Inspection | 6/11/2012 | 6/12/2012 | 6/12/2012 9:30:34 AM | A | PASS |
|
|
Life safety passed.
|
FIR12-00258
| INSP-Final Inspection | 6/11/2012 | 6/12/2012 | 6/12/2012 9:30:07 AM | A | PASS |
|
|
Permit finaled
|
FIR12-00281
| INSP-Final Inspection | 6/11/2012 | 6/12/2012 | 6/12/2012 8:21:38 AM | A | PASS |
|
|
Permit finaled
|