Inspections for the day of: Friday, June 12, 2015.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MIS15-00133 ELE-Final6/11/20156/12/20156/12/2015 12:56:20 PMAFAIL
Randy Phone #: ###-#### NEC 210.8(B)(5) All 15 and 20 ampere 120 volt receptacles within 6ft. of an sink, basin shall have GFCI protection. NEC 408.7 Unused openings for circuit breakers and switches shall be closed using identifed closures.
ELE14-03488 Final6/11/20156/12/20156/12/2015 11:04:28 AMANR
Shawn Case Phone #: ###-#### Inspection requested via web by Kerri Hamilton Not ready at this time, will reschedule for PM inspection
ELE15-01752 Electrical Rough-In6/11/20156/12/20156/12/2015 10:59:52 AMAPASS
garage code #1164 Phone #: ###-#### Inspection requested via web by Eric Schroeder rough-in ok cover kitchen remodel
ELE15-01755 Temporary Service6/11/20156/12/20156/12/2015 10:39:22 AMAPASS
Phone #: ###-#### Inspection requested via web by TOM BICANDI t/s u/g n ok
ELE15-00108 Final6/11/20156/12/20156/12/2015 9:25:24 AMAPASS
Phone #: ###-#### Inspection requested via web by steve ragan correction done, final ok