Inspections for the day of: Friday, June 12, 2015.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorThomas Walsh
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00681 INSP-Sprinkler Rough-in/Hydro6/12/20156/12/20156/12/2015 7:30:34 PMPPASS
Final Inspection of Bldg D wet pipe fire sprinkler system.NOTE: One remaining item to be addressed under this permit is to extend the FDC connection adjacent to the main entry lobby from its current location to extend past the roof column that it is currently obstructed by. The contractor agreed to get this done - the final acceptance was issued with this agreement.
FIR14-00362 INSP-Sprinkler Rough-in/Hydro6/12/20156/12/20156/12/2015 7:24:15 PMPPASS
Final Inspection of under ground parking for wings A, B C, including the fire pump room. All fire alarm interface, such as waterflow and tampers were tested with the fire alarm system. Riser placards were applied. No discrepancies remained for this portion of the overall system.
FIR15-00096 INSP-Sprinkler Rough-in6/11/20156/12/20156/12/2015 3:57:17 PMPPART
RTC inspection for soffit lids for 3rd floor West units, including units 308, 319, 321, 322, 323, 324, 325, 326, 327, 328, 329, 330, 331, 333, 332, 335, 334, 337, 341, 340, 342, - Units 336, 339, and were already done. This should complete both wings of 3rd floor for unit soffit inspections.
FIR14-00727 INSP-Final Inspection6/12/20156/12/20156/12/2015 3:52:50 PMAFAIL
Final inspection of fire alarm system for Bldg D and common areas.
One HVAC duct detector is not shutting down its assoc, HVAC unit. Three other units tested OK.
FIR14-00729 INSP-Final Inspection6/12/20156/12/20156/12/2015 3:51:05 PMAPART
Final inspection of fire alarm systems for Wings C & D, including elevator recall functions and SFDs - PASSED
FIR14-00330 INSP-Final Inspection6/12/20156/12/20156/12/2015 3:49:34 PMAPASS
Final inspection of Wings A & B buildings, including elevator recall functions, and SFDs - PASSED
FIR14-00271 INSP-Final Inspection6/12/20156/12/20156/12/2015 3:47:44 PMAPASS
Final inspection of fire alarm components for the garage level of Wings A,B,C and D, including all initiating devices, including MPs, elevator recall functions, SFDs, notification devices, etc
FIR14-00344 INSP-Final Inspection6/11/20156/12/20156/12/2015 3:44:27 PMAPASS
Final inspection of A, B & C wings - wet pipe systems.ALL PASSED. Fire alarm system interface also finaled this day.
FIR13-00167 INSP-Sprinkler Rough-in/Hydro6/11/20156/12/20156/12/2015 3:39:56 PMAPART
Thrust block inspection of fire service underground supply line and FDC supply line for 11th street connection - hydrotest could not be conducted because city connection could not be made, due to a faulty connector. The contractor assumes all risk of burying pipe prior to hydrotest.