FIR14-00681
| INSP-Sprinkler Rough-in/Hydro | 6/12/2015 | 6/12/2015 | 6/12/2015 7:30:34 PM | P | PASS |
|
|
Final Inspection of Bldg D wet pipe fire sprinkler system.NOTE: One remaining item to be addressed under this permit is to extend the FDC connection adjacent to the main entry lobby from its current location to extend past the roof column that it is currently obstructed by. The contractor agreed to get this done - the final acceptance was issued with this agreement.
|
FIR14-00362
| INSP-Sprinkler Rough-in/Hydro | 6/12/2015 | 6/12/2015 | 6/12/2015 7:24:15 PM | P | PASS |
|
|
Final Inspection of under ground parking for wings A, B C, including the fire pump room. All fire alarm interface, such as waterflow and tampers were tested with the fire alarm system. Riser placards were applied. No discrepancies remained for this portion of the overall system.
|
FIR15-00096
| INSP-Sprinkler Rough-in | 6/11/2015 | 6/12/2015 | 6/12/2015 3:57:17 PM | P | PART |
|
|
RTC inspection for soffit lids for 3rd floor West units, including units 308, 319, 321, 322, 323, 324, 325, 326, 327, 328, 329, 330, 331, 333, 332, 335, 334, 337, 341, 340, 342, - Units 336, 339, and were already done. This should complete both wings of 3rd floor for unit soffit inspections.
|
FIR14-00727
| INSP-Final Inspection | 6/12/2015 | 6/12/2015 | 6/12/2015 3:52:50 PM | A | FAIL |
|
|
Final inspection of fire alarm system for Bldg D and common areas. One HVAC duct detector is not shutting down its assoc, HVAC unit. Three other units tested OK.
|
FIR14-00729
| INSP-Final Inspection | 6/12/2015 | 6/12/2015 | 6/12/2015 3:51:05 PM | A | PART |
|
|
Final inspection of fire alarm systems for Wings C & D, including elevator recall functions and SFDs - PASSED
|
FIR14-00330
| INSP-Final Inspection | 6/12/2015 | 6/12/2015 | 6/12/2015 3:49:34 PM | A | PASS |
|
|
Final inspection of Wings A & B buildings, including elevator recall functions, and SFDs - PASSED
|
FIR14-00271
| INSP-Final Inspection | 6/12/2015 | 6/12/2015 | 6/12/2015 3:47:44 PM | A | PASS |
|
|
Final inspection of fire alarm components for the garage level of Wings A,B,C and D, including all initiating devices, including MPs, elevator recall functions, SFDs, notification devices, etc
|
FIR14-00344
| INSP-Final Inspection | 6/11/2015 | 6/12/2015 | 6/12/2015 3:44:27 PM | A | PASS |
|
|
Final inspection of A, B & C wings - wet pipe systems.ALL PASSED. Fire alarm system interface also finaled this day.
|
FIR13-00167
| INSP-Sprinkler Rough-in/Hydro | 6/11/2015 | 6/12/2015 | 6/12/2015 3:39:56 PM | A | PART |
|
|
Thrust block inspection of fire service underground supply line and FDC supply line for 11th street connection - hydrotest could not be conducted because city connection could not be made, due to a faulty connector. The contractor assumes all risk of burying pipe prior to hydrotest.
|