MEC18-02196
| Final | 6/7/2018 | 6/12/2018 | 6/12/2018 1:12:45 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Mary LaFayette
|
MEC18-01442
| Conference | 6/12/2018 | 6/12/2018 | 6/12/2018 10:24:32 AM | A | DONE |
|
|
Dale Pipkin is your contact for the conference. Phone #: ###-#### Inspection requested via web by Kim Adams - Met and discussed finishes around hood
|
MEC18-02517
| Rough-in | 6/8/2018 | 6/12/2018 | 6/12/2018 10:00:12 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Debbie Marino - 1) Exhaust fans not installed 2) Ducts not connected in the attic ( trunk lines at furnace). 3) 12" supply trunk line is smashed in the garage overbuild joists. 4) 6" fresh air needs to go to the return plenum, not the return can.
|
MEC18-02517
| Pressure Test | 6/8/2018 | 6/12/2018 | 6/12/2018 9:57:15 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Debbie Marino - 20lb gas, 5lb flue
|
MEC18-01613
| Pressure Test | 6/11/2018 | 6/12/2018 | 6/12/2018 9:38:01 AM | A | PASS |
|
|
Field super: Daryl Thomas Phone #: ###-#### Inspection requested via web by Lisa Whitney - 20lb gas
|
MEC18-01613
| Rough-in | 6/11/2018 | 6/12/2018 | 6/12/2018 9:37:42 AM | A | PASS |
|
|
Field super: Daryl Thomas Phone #: ###-#### Inspection requested via web by Lisa Whitney
|
MEC17-02986
| Mec-Aging Inspection | 6/12/2018 | 6/12/2018 | 6/12/2018 8:40:52 AM | | CANC |
|
|
Called contrator and left a message to schedule an inspection
|
MEC12-02306
| Mec-Aging Inspection | 6/12/2018 | 6/12/2018 | 6/12/2018 7:46:06 AM | | CANC |
|
|
|