Inspections for the day of: Tuesday, June 12, 2018.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00267 INSP-Sprinkler Rough-in/Hydro6/12/20186/12/20186/12/2018 5:27:16 PMPPART
Hydrostatic test for overhead fire sprinkler piping on level 1 witnessed, no pressure loss observed at riser provided gauge. Levels 2, 3, 4, 5 and standpipe to be completed at a later date.

Contact - Ken Orahood - ###-#### 30 min prior to Hydro Insp start on levels 1, 2 4 ; 5 please

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR18-00454 INSP-Final Inspection6/12/20186/12/20186/12/2018 1:59:42 PMPCANC
Fire alarms are not ready, fire alarm associated devices could no be tested, this inspection request is cancelled.

Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00095 INSP-Final Inspection6/12/20186/12/20186/12/2018 1:59:11 PMPCANC
Fire alarms are not ready, fire alarm associated devices could no be tested, this inspection request is cancelled.

Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00051 INSP-Final Inspection6/12/20186/12/20186/12/2018 1:58:48 PMPCANC
Fire alarms are not ready, fire alarm associated devices could no be tested, this inspection request is cancelled.

Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00316 INSP-Sprinkler Rough-in6/11/20186/12/20186/12/2018 10:15:23 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover. Wood columns are exposed above the ceiling grid, columns will need to be covered in sheetrock above the ceiling or upright protection will be required to protect the combustible material. Columns issue will be verified at a later date.

Phone #: ###-#### Inspection requested via web by Sam Ball
FIR18-00454 INSP-Final Inspection6/12/20186/12/20186/12/2018 9:23:15 AMPCANC
Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
FIR18-00451 INSP-Final Inspection6/11/20186/12/20186/12/2018 8:04:47 AMAPASS
Final commercial hood fire suppression system inspection complete.

Dave Phone #: ###-####
FIR18-00451 INSP-Sprinkler Rough-in/Hydro6/11/20186/12/20186/12/2018 8:03:12 AMACANC
Coordinated for 7AM with installing contractor.