Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR20-00125 INSP-Final Inspection6/12/20206/12/20206/12/2020 4:13:54 PMPPASS
Previously noted items have been corrected, final fire sprinkler inspection is complete, irrigation shutdown on flow switch activation witnessed.
BLD18-04070 FIRE-Final Inspection6/11/20206/12/20206/12/2020 4:11:57 PMPPASS
Final life fire safety inspection complete, signature provided on permit sign off card.

Phone #: ###-#### Inspection requested via web by chad stradley
FIR20-00168 INSP-Sprinkler Rough-in6/10/20206/12/20206/12/2020 1:19:26 PMPFAIL
Make corrections on drop down nipple 90's as discussed.

Richard Clark is the contact. Thanks! (: Phone #: ###-#### Inspection requested via web by Stan Beus
FIR20-00262 INSP-Final Inspection6/9/20206/12/20206/12/2020 11:29:44 AMAFAIL
Add device in room, basement level as discussed. Lower 4 devices due to blockage of ceiling soffit, soffit block affect of strobe. Move smoke detector that is too far down from the ceiling as discussed.

Please call 15-20 minutes prior to arrival, you will be meeting Justin Volquardsen on site.
Phone #: ###-#### Inspection requested via web by jason petty
FIR20-00364 INSP-Final Inspection6/9/20206/12/20206/12/2020 11:27:43 AMAPASS
Final fire alarm inspection for scope of work is complete.

Phone #: ###-#### Inspection requested via web by jason petty
FIR20-00302 INSP-Final Inspection6/9/20206/12/20206/12/2020 10:56:33 AMACANC
This is to final the elevator. The state elevator inspector will also be on site.
Contact Jeff Roberts at 208###-#### when on site, This inspection is at Building 80 Phone #: ###-#### >> Inspection requested via web by Jeff Roberts Inspection cancelled from web by: Jeff Roberts
BLD20-01033 FIRE-Final Inspection6/11/20206/12/20206/12/2020 9:36:46 AMAFAIL
Fire sprinkler head on the elevator lobby side of door is overspaced, max distance is 7ft 6in off of wall. Need doors and door hardware placed and operational before life fire safety can be signed off.

Screened- Jeff Phone #: ###-####