Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00175 INSP-Sprinkler Rough-in6/12/20036/13/20036/13/2003 12:00:00 AMAFAIL
john; Phone #: ###-#### The wet system in the west entry lobby has the incorrect pipe size. Treasure valley to resubmit calculations to prove size is ok. Upright sprinkler heads along the west wall are overspaced off the wall. Per the contractor he will have the insulation people install additional insulation. The insulation will need to be within 6'-0" of the branchline the entire lenght of the wall. Two armovers in the southeast corner of the central section will need to be lenghtened by 10" to fix an overspacing problem. The east entry wet and dry piping and the tenting is not complete yet. Sprinkler piping not to be covered 6/13/2003 12:20:20 PM