Inspections for the day of: Monday, June 13, 2005.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-01632 FIRE-Sprinkler Rough-in6/13/20056/13/20056/13/2005 4:50:42 PMPFAIL
###-#### Bob Underground fire supply storage tanks appear to have been installed without a fire permit. This work must cease until a fire permit is obtained or verification is given that this work is allowed under BLD04-01632.
MIS04-00258 FIR-Final6/9/20056/13/20056/13/2005 2:55:34 PMAFAIL
Fire extinguishers are still not provided, tagged and installed as noted by previous inspection in Sept. of 04.
FIR05-00119 INSP-Sprinkler Rough-in/Hydro6/13/20056/13/20056/13/2005 1:42:06 PMPPART
Overhead hydrostatic test passed. Overhead rough-in satisfactory except one upright head on 2nd floor directly below deck opening for HVAC.
FIR05-00265 INSP-Sprinkler Rough-in6/13/20056/13/20056/13/2005 1:22:27 PMPPART
Underground fire supply line riser piece and 5' stub out OK to cover. Still need provision for EQ clearance through floor slab.
FIR05-00062 INSP-Final Inspection6/13/20056/13/20056/13/2005 12:22:44 PMPPART
Remainder of rough-in at kitchen area OK to cover. Need ceiling tile installed at heads, foreward flow and alarms for final.
BLD04-02970 FIRE-Final Inspection6/13/20056/13/20056/13/2005 12:18:33 PMPPASS
Fire life safety passed inspection. Sign off card for CO not available on site at the time of inspection, notified the general contractor.
FIR05-00260 INSP-Sprinkler Rough-in6/10/20056/13/20056/13/2005 9:38:37 AMAPART
Overhead rough-in OK for cover. Need to provide watts backflow preventer as submitted or prove calcs on installed wilkins model are the same.