Inspections for the day of: Tuesday, June 13, 2006.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01300 Electrical Rough-In6/13/20066/13/20066/13/2006 4:07:28 PMPFAIL
LAIS; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. called 300.4 (A)(1)&(D) nail plates and 11/4", 210.52(A) outlet spacing bedrm.210.52(H) outlet for hall, 250.148 splice all equip grds #12 and 14 2 gang kit, complete makeup equip grds heaters, update permit for elect heat, make sure apartment numbers are in notes
ELE06-00305 Final6/13/20066/13/20066/13/2006 3:18:26 PMPPASS
Scheduled by a contractor via Hello! on 6/13/2006 at 10:16:57 AM. Contact: ###-####. ok
ELE06-01523 Electrical Rough-In6/13/20066/13/20066/13/2006 2:57:15 PMPPASS
###-#### - tyler ok corr. made
ELE06-02096 Electrical Rough-In6/12/20066/13/20066/13/2006 2:36:10 PMPPART
Brian; Phone #: ###-#### r/i house ok
ELE06-02096 Permanent Service6/13/20066/13/20066/13/2006 2:35:46 PMPPASS
Brian; Phone #: ###-#### r/i p/s u/g new ok
ELE06-01698 Final6/13/20066/13/20066/13/2006 2:17:12 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Tyler Bowen ok card signed
ELE06-02069 Electrical Rough-In6/13/20066/13/20066/13/2006 1:45:35 PMPPART
Scheduled by a contractor via Hello! on 6/13/2006 at 7:55:57 AM. Contact: ###-####. r/i ok anop
ELE06-02173 Electrical Rough-In6/13/20066/13/20066/13/2006 1:02:20 PMPNR
neil ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called needs set of approved plans for basement, some nail plates, protect cables 6ft of attic access
ELE05-04145 Final6/12/20066/13/20066/13/2006 12:25:34 PMANH
Scheduled by a contractor via Hello! on 6/12/2006 at 4:15:31 PM. Contact: ###-####. called
ELE06-02131 Electrical Rough-In6/12/20066/13/20066/13/2006 12:00:34 PMPPART
Re-Inspection of conduit/trench.; Phone #: ###-#### Internet Inspection Request from: Julie Schroder u/g ok
ELE06-00711 Electrical Rough-In6/12/20066/13/20066/13/2006 10:45:54 AMAPART
Scheduled by a contractor via Hello! on 6/12/2006 at 1:34:24 PM. interior side of penthouse wall and prarpet wall anop
ELE06-01630 Final6/13/20066/13/20066/13/2006 9:58:31 AMAPASS
wall signs ok
ELE06-00808 Final6/12/20066/13/20066/13/2006 9:57:40 AMAPASS
please call ahead-30 min. Thank you; Phone #: ###-#### Internet Inspection Request from: Kerri ok card signed
ELE06-01523 Electrical Rough-In6/12/20066/13/20066/13/2006 9:20:38 AMAFAIL
morgan; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
corr. not made called box fill liv rm westand east wall steel cutins and gas range outlet
ELE06-02107 Permanent Service6/13/20066/13/20066/13/2006 8:11:07 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Phil Baker p/s o/h rec. ok
ELE06-02096 Electrical Rough-In6/12/20066/13/20066/13/2006 12:00:00 AMACANC
Brian; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt reschedules brian