Inspections for the day of: Tuesday, June 13, 2006.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-02022 Electrical Rough-In6/13/20066/13/20066/13/2006 4:32:57 PMPPASS
randy - groundwork insp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to cover u/g
ELE06-00456 Electrical Rough-In6/13/20066/13/20066/13/2006 4:32:14 PMPPASS
randy - groundwork insp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to cover u/g
ELE06-02172 Final6/13/20066/13/20066/13/2006 4:08:26 PMPPASS
Stu; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to final
ELE06-01464 Final6/13/20066/13/20066/13/2006 3:43:28 PMPFAIL
Scheduled by a contractor via Hello! on 6/13/2006 at 7:35:31 AM. Contact: ###-####. called, left corr notice, nec 408.4 every circuit shall be identified to its clear, evident and specific purpose, 406.5 cover plates shall seat against mounting surface, 406.4(D) recpt faces shall be flush with or project from faceplates, 440.4(A) a/c shall be provided wirh nameplate, 422.31(B) dishwasher shall have lock-out provisions,BCC disposal shall be wired
ELE06-02155 Electrical Rough-In6/12/20066/13/20066/13/2006 3:01:13 PMPCANC
bonding and partial underground for new pool.; Phone #: ###-#### Internet Inspection Request from: joe wheeler contr called to cancel for pm, will recall
ELE06-00117 Electrical Rough-In6/13/20066/13/20066/13/2006 2:52:13 PMPPART
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover showroom area hardlids, s & e walls north part of bldg
ELE06-02150 Temporary Service6/12/20066/13/20066/13/2006 2:20:18 PMPPASS
Brandon; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt t/s u/g n ok
ELE06-01193 Electrical Rough-In6/13/20066/13/20066/13/2006 2:08:36 PMPPASS
LARRY - nOTE: UNDERGROUND; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles u/g ok to cover
ELE06-02165 Temporary Service6/13/20066/13/20066/13/2006 1:09:03 PMPFAIL
pat; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 250.24 (A) gec shall connect to gnded conductor terminal
ELE06-02161 Temporary Service6/13/20066/13/20066/13/2006 1:05:02 PMPFAIL
olga; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called,left message, lrft corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 110.12(C) there shall be no broken parts, 310.16 max ampacity 15A for #14 wire to 120v recpt
ELE06-01070 Final6/13/20066/13/20066/13/2006 11:48:14 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Shane Vigil ok to final
ELE06-02130 Rough-In Permanent Service6/9/20066/13/20066/13/2006 10:55:48 AMAFAIL
###-#### - steve talked to contr, left corr notice, nec 300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing member, BCC all make-up shall be done
ELE06-02012 Rough-In Permanent Service6/9/20066/13/20066/13/2006 10:44:16 AMAFAIL
Scheduled by a contractor via Hello! on 6/9/2006 at 10:19:04 AM. Contact: ###-####. talked to contr, left corr notice, nec 300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing member,334.80 more than 2 nm cables shall be derated per 310.15(B)(2) that are bundled through wood framing that is to be draft stopped
ELE06-02160 Electrical Rough-In6/12/20066/13/20066/13/2006 10:14:53 AMAPASS
swimming pool bonding Internet Inspection Request from: Rowdy Monroe pool bond only ok, no u/g done
ELE06-01985 Rough-In Permanent Service6/12/20066/13/20066/13/2006 9:12:46 AMAPASS
Scheduled by a contractor via Hello! on 6/12/2006 at 4:49:58 PM. Contact: ###-####. corr made, ric ok, p/s u/g n ok
ELE06-00113 Electrical Rough-In6/12/20066/13/20066/13/2006 8:51:24 AMAPART
Contact Greg Pack. Ceiling rough-in 10th floor; Phone #: ###-#### Internet Inspection Request from: Shelli Daylong 10th floor clgs, 5th walls anop ok to cover