Inspections for the day of: Wednesday, June 13, 2007.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-02142 Final6/13/20076/13/20076/15/2007 9:53:20 AMPPASS
Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer street lights need to be inspected by public works
ELE07-00920 Final6/13/20076/13/20076/13/2007 3:28:39 PMPFAIL
reinspection Phone #: ###-#### Internet Inspection Request from: DJ Carman corr called 110.3(B) needs 25 amp for a/c not WH, or your circuit directory is not specific as to purpose and use, 334.23 all 3 homes, shall remove NMB from attic accesses and protect as code noted states
ELE07-00918 Final6/13/20076/13/20076/13/2007 3:15:57 PMPFAIL
reinspection Phone #: ###-#### Internet Inspection Request from: DJ Carman
corr. called 110.3(B) & 422.11(A) shall provide max protection of 25 amps for a/c they changed the W H breaker ,or circuit directory is wrong
ELE07-00917 Final6/13/20076/13/20076/13/2007 3:11:13 PMPPASS
reinspection Phone #: ###-#### Internet Inspection Request from: DJ Carman ok
ELE07-02010 Electrical Rough-In6/13/20076/13/20076/13/2007 2:01:39 PMPPASS
rough in for kitchen remodel any questions call tate @###-#### Phone #: ###-#### Internet Inspection Request from: Andy Rose kit remodel wiring ok
ELE07-02118 Electrical Rough-In6/13/20076/13/20076/13/2007 1:30:54 PMPPASS
ok to cover, cell ###-#### Randy Phone #: ###-#### Internet Inspection Request from: Randy Fletcher kit. din rm remodel wiring ok
ELE07-02108 Electrical Rough-In6/13/20076/13/20076/13/2007 1:01:00 PMPPASS
underground from house to column Phone #: ###-#### Internet Inspection Request from: Monty Adkinson ok corr. made
ELE07-01836 Electrical Rough-In6/13/20076/13/20076/13/2007 12:36:54 PMPNR
chris - pool - aqua potenetial plane ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called not ready and E grid shall be install per electrical news brief , instructions
ELE07-01641 Electrical Rough-In6/12/20076/13/20076/13/2007 12:17:07 PMAPART
u/g conduit installtion ok new service lateral
ELE07-02114 Final6/12/20076/13/20076/13/2007 10:09:41 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer this is a state job for elevator equip rm state posted correction
ELE07-02116 Final6/12/20076/13/20076/13/2007 10:05:49 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer called needs raceway or cable too protect wires outside recepts open wiring in wall
ELE07-02116 Electrical Rough-In6/13/20076/13/20076/13/2007 10:01:06 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer called see final for notes
ELE07-02128 Permanent Service6/12/20076/13/20076/13/2007 9:13:53 AMAFAIL
allen ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
corr. called 110.9&10 fault and short-circuit current for p/s for sprinkle time clock 2ft for
IDPO x-former
ELE07-02128 Final6/13/20076/13/20076/13/2007 8:55:36 AMANR
allen ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
ELE07-01251 Final6/11/20076/13/20076/13/2007 8:34:44 AMAFAIL
Thank you Phone #: ###-#### Internet Inspection Request from: Tracy Robertson
called carpet in the way , stacked by walls