Inspections for the day of: Friday, June 13, 2008.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-04225 ELE-Aging Inspection6/13/20086/13/20086/16/2008 9:14:20 AM DONE
see final
ELE08-01595 Permanent Service6/13/20086/13/20086/13/2008 3:46:59 PMPNR
Eric Phone #: ###-#### met contractor, nothing set, no grounding, ipco would not come out because contractor called too late
ELE06-04386 ELE-Aging Inspection6/13/20086/13/20086/13/2008 2:51:11 PM DONE
ok see final, no esc
ELE06-04386 Final6/13/20086/13/20086/13/2008 2:50:16 PMPPASS
looked at signs, ok to final, no esc
ESC08-00375 General Inspection6/13/20086/13/20086/13/2008 2:46:38 PMPPASS
looked ok
ELE08-01384 Electrical Rough-In6/13/20086/13/20086/13/2008 2:45:00 PMPPASS
Mike- pool bonding, please check light potting Phone #: ###-#### pool bonding and potting only ok
ELE08-01549 Final6/13/20086/13/20086/13/2008 2:01:38 PMPFAIL
Kelly Tarter ###-#### Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson called, left correction notice,NEC 408.4 shall provide circuit directories and be clear and concise, 312.5 shall provide abrasion protection for all conductors entering enclosures, 352.30(A) rnc shall be securely supported within 3' of termination,250.24(A) grounding electrode conductor shall be connected to grounded conductor at service, 250.28 shall provide main bonding jumper, 250.53(G) grounding electrode conductor shall be attached to rod, 406.8(B) shall use in-use type receptacle cover, 356.30 lfnc shall be supported within 12" of termination, 110.3(B) listed equipment shall be installed per instructions included, no esc
ELE08-01514 Final6/10/20086/13/20086/13/2008 1:41:58 PMPPASS
final for service & circuit to A/C Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok to final, no esc
ESC08-00035 General Inspection6/13/20086/13/20086/13/2008 10:34:27 AMAPART
looked ok
ELE08-01576 Temporary Service6/13/20086/13/20086/13/2008 10:28:38 AMAPASS
correction made, t/s o/h n ok, no esc
ELE08-01563 Electrical Rough-In6/12/20086/13/20086/13/2008 10:25:13 AMAPASS
Jim Phone #: ###-#### u/g ok for deep conduit,i.e. parking lot lighting and 2" along with communication conduit, will see below slab at another inspection, note ufer was done under another contractor
ELE06-04665 Final6/12/20086/13/20086/13/2008 10:04:35 AMPCANC
boun Phone #: ###-#### Inspection cancelled from web by: Alexandra Rahn
ELE08-01592 Final6/12/20086/13/20086/13/2008 10:04:32 AMANR
Phone #: ###-#### Internet Inspection Request from: Lee Braithwait met electricians, meant to call for pm, pole not moved, fee due, no esc
ELE08-01578 Permanent Service6/12/20086/13/20086/13/2008 9:29:36 AMAPASS
Phone #: ###-#### Internet Inspection Request from: BRENDA HURST p/s u/g n ok, no esc this permit
ELE08-01576 Final6/12/20086/13/20086/13/2008 8:56:35 AMAPASS
please re inspect temp pole for fixed corrections Phone #: ###-#### Internet Inspection Request from: steve creswell corrections made, t/s o/h n ok, no esc this permit
ELE08-01029 Electrical Rough-In6/12/20086/13/20086/13/2008 8:02:21 AMAPASS
Danny; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to cover ceiling in take-n-bake area anop only