FIR08-00290
| INSP-Final Inspection | 6/12/2008 | 6/13/2008 | 6/13/2008 4:28:13 PM | P | PART |
|
|
See the approved plans for piping at the pizza place that can be covered. I let Rick know that one additional upright will be required in the combustible space. I will verify this upright at the next inspection.
|
FIR07-00969
| INSP-Final Inspection | 6/13/2008 | 6/13/2008 | 6/13/2008 4:26:38 PM | P | FAIL |
|
|
The electric alarm bell has not been connected to the fire alarm panel. It has actually been connected to the forward flush control valve. When I operated the valve sparks flew from the junction box. Also the FDC is mounted below 18". Per the plans it was to be installed at 30". Need to perform forward flush as well.
|
FIR08-00358
| INSP-Final Inspection | 6/12/2008 | 6/13/2008 | 6/13/2008 4:25:20 PM | P | FAIL |
|
|
The electric alarm bell has not been connected to the fire alarm panel. It has actually been connected to the forward flush control valve. When I operated the valve sparks flew from the junction box.
|
BLD08-00575
| FIRE-Final Inspection | 6/13/2008 | 6/13/2008 | 6/13/2008 4:23:40 PM | P | CANC |
|
|
Wrong inspection type called in.
|
BLD08-00328
| FIRE-Final Inspection | 6/12/2008 | 6/13/2008 | 6/13/2008 11:46:27 AM | A | PASS |
|
|
Life safety passed.
|
FIR08-00323
| INSP-Final Inspection | 6/12/2008 | 6/13/2008 | 6/13/2008 11:06:13 AM | A | FAIL |
|
|
Inspection was not ready for a final due to ceiling tile missing and the 2 1/2" couplings at the top and bottom of the relocated riser piece were leaking.
|
BLD08-01249
| FIRE-Final Inspection | 6/12/2008 | 6/13/2008 | 6/13/2008 9:48:14 AM | A | PASS |
|
|
Life safety passed.
|