Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00290 INSP-Final Inspection6/12/20086/13/20086/13/2008 4:28:13 PMPPART
See the approved plans for piping at the pizza place that can be covered. I let Rick know that one additional upright will be required in the combustible space. I will verify this upright at the next inspection.
FIR07-00969 INSP-Final Inspection6/13/20086/13/20086/13/2008 4:26:38 PMPFAIL
The electric alarm bell has not been connected to the fire alarm panel. It has actually been connected to the forward flush control valve. When I operated the valve sparks flew from the junction box. Also the FDC is mounted below 18". Per the plans it was to be installed at 30". Need to perform forward flush as well.
FIR08-00358 INSP-Final Inspection6/12/20086/13/20086/13/2008 4:25:20 PMPFAIL
The electric alarm bell has not been connected to the fire alarm panel. It has actually been connected to the forward flush control valve. When I operated the valve sparks flew from the junction box.
BLD08-00575 FIRE-Final Inspection6/13/20086/13/20086/13/2008 4:23:40 PMPCANC
Wrong inspection type called in.
BLD08-00328 FIRE-Final Inspection6/12/20086/13/20086/13/2008 11:46:27 AMAPASS
Life safety passed.
FIR08-00323 INSP-Final Inspection6/12/20086/13/20086/13/2008 11:06:13 AMAFAIL
Inspection was not ready for a final due to ceiling tile missing and the 2 1/2" couplings at the top and bottom of the relocated riser piece were leaking.
BLD08-01249 FIRE-Final Inspection6/12/20086/13/20086/13/2008 9:48:14 AMAPASS
Life safety passed.