Inspections for the day of: Thursday, June 13, 2013.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00252 INSP-Alarm Testing6/12/20136/13/20136/17/2013 8:02:08 AMPFAIL
New notification appliances need to meet location guidelines per NFPA 72. Type and cd settings need to match approved plan. DSC permit must be finaled prior.
FIR13-00116 INSP-Sprinkler Rough-in6/12/20136/13/20136/17/2013 7:57:09 AMPPART
Overhead rough-in at the west and east side restrooms, RR vestibules, and patio areas are approved for cover as marked and dated on stamped plan set.
FIR13-00243 INSP-Sprinkler Rough-in6/13/20136/13/20136/17/2013 7:51:58 AMPPART
Overhead rough-in inspection completed- field modifications to be reflected on as-builts. Cover approval pending verification of insulation for cold cavity protection.
BLD13-01382 FIRE-Final Inspection6/12/20136/13/20136/14/2013 6:40:04 AMAPASS
Fire life safety inspection passed - manual thumbturns at the main entry/exit to be removed prior to structural final as agreed.
BLD13-01472 FIRE-Final Inspection6/12/20136/13/20136/13/2013 11:25:14 AMAPASS
Life safety inspection passed provided commercial grade single function hardware is provided at the new door per plan red-line annotations. Also need to post "door to remain.." signage at the main entry/exit door. Items to be finished prior to structural final as discussed.