FIR13-00440
| INSP-Sprinkler Rough-in | 6/9/2014 | 6/9/2014 | | P | |
|
|
Terry at phone #: ###-####
|
BLD14-00165
| FIRE-Final Inspection | 6/13/2014 | 6/13/2014 | 6/13/2014 4:57:21 PM | P | PASS |
|
|
Fire life safety finaled. Inspection passed.
|
FIR14-00329
| INSP-Final Inspection | 6/12/2014 | 6/13/2014 | 6/13/2014 4:56:17 PM | P | PASS |
|
|
Fire alarm work passed field testing and inspection. Permit finaled.
|
FIR13-00440
| INSP-Sprinkler Rough-in | 6/13/2014 | 6/13/2014 | 6/13/2014 3:05:38 PM | P | PART |
|
|
EC heads at the banquet room 1st floor approved for cover. Re-inspection at the main street entry vestibule and lobby okayed. Noted the need to remove valves in sensing lines at the FP and JP.
|
BLD14-00522
| FIRE-Final Inspection | 6/12/2014 | 6/13/2014 | 6/13/2014 1:47:31 PM | A | PASS |
|
|
Scope of work completed. Inspection passed, no signature card available on site .
|
FIR13-00409
| INSP-Sprinkler Rough-in | 6/12/2014 | 6/13/2014 | 6/13/2014 12:41:50 PM | A | PART |
|
|
Randy Phone #: ###-####
|
FIR14-00231
| INSP-Sprinkler Rough-in | 6/12/2014 | 6/13/2014 | 6/13/2014 12:41:02 PM | A | PART |
|
|
Overhead install at the kitchen and bakery areas per the scope of work passed rough-in inspection. * Need to provide a QR head in the bakery cooler.
|
FIR13-00440
| INSP-Sprinkler Rough-in | 6/12/2014 | 6/13/2014 | 6/13/2014 12:37:18 PM | A | FAIL |
|
|
Inspection for overhead cover at the 1st floor main street side entry lobby and vestibule failed due to overspaced pendent heads and missing hanger at the main.
|