Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00440 INSP-Sprinkler Rough-in6/9/20146/9/2014 P 
Terry at phone #: ###-####
BLD14-00165 FIRE-Final Inspection6/13/20146/13/20146/13/2014 4:57:21 PMPPASS
Fire life safety finaled. Inspection passed.
FIR14-00329 INSP-Final Inspection6/12/20146/13/20146/13/2014 4:56:17 PMPPASS
Fire alarm work passed field testing and inspection. Permit finaled.
FIR13-00440 INSP-Sprinkler Rough-in6/13/20146/13/20146/13/2014 3:05:38 PMPPART
EC heads at the banquet room 1st floor approved for cover. Re-inspection at the main street entry vestibule and lobby okayed. Noted the need to remove valves in sensing lines at the FP and JP.
BLD14-00522 FIRE-Final Inspection6/12/20146/13/20146/13/2014 1:47:31 PMAPASS
Scope of work completed. Inspection passed, no signature card available on site .
FIR13-00409 INSP-Sprinkler Rough-in6/12/20146/13/20146/13/2014 12:41:50 PMAPART
Randy Phone #: ###-####
FIR14-00231 INSP-Sprinkler Rough-in6/12/20146/13/20146/13/2014 12:41:02 PMAPART
Overhead install at the kitchen and bakery areas per the scope of work passed rough-in inspection. * Need to provide a QR head in the bakery cooler.
FIR13-00440 INSP-Sprinkler Rough-in6/12/20146/13/20146/13/2014 12:37:18 PMAFAIL
Inspection for overhead cover at the 1st floor main street side entry lobby and vestibule failed due to overspaced pendent heads and missing hanger at the main.