Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00606 INSP-Sprinkler Rough-in6/13/20176/13/20176/13/2017 2:06:05 PMPPART
Corrections have been made in rooms where too many heads were installed of off 1 inch pipe (see city approved drawings where rooms were noted with yellow highlighter and red ink indicating no cover) Rooms that were noted are approved for cover. North side of elevator lobby level 5 has been inspected, piping cannot be covered until an inspection has been performed to verify that there is a clear pocket between the sheetrock and overhead fire sprinkler piping/insulation for freeze prevention.
FIR16-00821 INSP-Sprinkler Rough-in6/12/20176/13/20176/13/2017 1:11:33 PMPPART
See the city approved plans for locations where piping can be covered marked with todays date.
FIR16-00267 INSP-Sprinkler Rough-in6/13/20176/13/20176/13/2017 12:25:12 PMPPART
Rough to cover inspection for overhead fire sprinkler piping located above hardlids in the B side 7th floor complete (west wing) hardlids approved for cover.
BLD17-00849 FIRE-Final Inspection6/12/20176/13/20176/13/2017 9:55:21 AMAPASS
Fire sprinkler inspection is complete, fire alarm inspection for building is complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
BLD17-00942 FIRE-Final Inspection6/12/20176/13/20176/13/2017 9:39:20 AMAPASS
Fire alarm complete, no fire sprinklers, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
FIR17-00221 INSP-Final Inspection6/12/20176/13/20176/13/2017 9:38:26 AMAPASS
Final fire alarm inspection passed/complete
BLD17-00585 FIRE-Conference6/12/20176/13/20176/13/2017 8:38:44 AMADONE
Fire conference complete
BLD17-01786 FIRE-Final Inspection6/13/20176/13/20176/13/2017 8:03:22 AMAPASS
No fire sprinklers, no fire alarms, emergency shutoff for fuel island is clearly visible, fire extinguisher has current inspection tag, exit light/emergncy lighting has been serviced and is operational. Final life fire safety inspection passed/complete.