Inspections for the day of: Wednesday, June 13, 2018.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-02196 Electrical Rough-In6/13/20186/13/20186/13/2018 3:00:00 PMPPASS
call 10 mins ahead- Thomas Phone #: ###-####-please go after 2 if possible-Thomas has a dentist app @ 12-if you can't go that late please call Thomas
Bathroom rough in ok cover
ELE18-02126 Permanent Service6/13/20186/13/20186/13/2018 2:30:26 PMPPASS
We are requesting a Permanent Service inspection for this project.
Our contact is Larry, ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Larry Looney p/s u/g n ok
ELE17-01337 Final6/13/20186/13/20186/13/2018 2:29:49 PMPPART
2nd ; 3rd floors. Phone #: ###-#### Inspection requested via web by Clint Tate Guest rooms levels 2 thru 5 all tested OK
ELE18-01012 Final6/12/20186/13/20186/13/2018 12:08:28 PMAFAIL
garage code 9124 Phone #: ###-#### Inspection requested via web by Darryn Coburn
110.12- Electrical equipment shall not be damaged. Expansion joint broke.
210.8- All receptacle outlets located with in 6' of a sink shall have GFCI protection. Family room receptacle.
422.31- Appliances where receptacle is not accessible lockout shall be inplace. Micro, lock out on 2 garage circuits.
Provide access to vacuum recptacle for testing.
ELE18-01013 Final6/12/20186/13/20186/13/2018 12:01:48 PMAFAIL
garage code 9224 Phone #: ###-#### Inspection requested via web by Darryn Coburn
110.26- Minimum work space shall be provided for meter base. 30" wide and 36" deep.
ELE17-02862 Electrical Rough-In6/13/20186/13/20186/13/2018 11:08:44 AMAPASS
Units 502 , 503 , 504 , 512 , 515 , 516 , 517 , 518 , 519 , elevator equipment room , trash rm , storage rms and 5th floor hallway call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Areas noted walls and fire lids rough in ok cover
ELE18-02126 Final6/12/20186/13/20186/13/2018 10:30:17 AMAFAIL
We are requesting a final inspection for this project. Our contact is Larry
###-#### Phone #: ###-#### Inspection requested via web by Larry Looney
250.8(A)(6)- Thread forming machine screws that engage not less than 2 threads in the enclosure shall be used.
Permanent service inspection must be approved prior to final inspection. At final shall be labelled and circuit free of shorts.
ELE18-01563 Final6/12/20186/13/20186/13/2018 9:54:31 AMAFAIL
Code to get in the door is
12340 Phone #: ###-#### Inspection requested via web by Bud Medcoff
210.8(B)(5)- All single phase receptacles 50 amp or less located with in 6' of a sink shall have GFCI protection.
210.62- At least one 125 volt 15 or 20 amp receptacle outlet shall be installed for show window.