ELE18-02196
| Electrical Rough-In | 6/13/2018 | 6/13/2018 | 6/13/2018 3:00:00 PM | P | PASS |
|
|
call 10 mins ahead- Thomas Phone #: ###-####-please go after 2 if possible-Thomas has a dentist app @ 12-if you can't go that late please call Thomas Bathroom rough in ok cover
|
ELE18-02126
| Permanent Service | 6/13/2018 | 6/13/2018 | 6/13/2018 2:30:26 PM | P | PASS |
|
|
We are requesting a Permanent Service inspection for this project. Our contact is Larry, ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Larry Looney p/s u/g n ok
|
ELE17-01337
| Final | 6/13/2018 | 6/13/2018 | 6/13/2018 2:29:49 PM | P | PART |
|
|
2nd ; 3rd floors. Phone #: ###-#### Inspection requested via web by Clint Tate Guest rooms levels 2 thru 5 all tested OK
|
ELE18-01012
| Final | 6/12/2018 | 6/13/2018 | 6/13/2018 12:08:28 PM | A | FAIL |
|
|
garage code 9124 Phone #: ###-#### Inspection requested via web by Darryn Coburn 110.12- Electrical equipment shall not be damaged. Expansion joint broke. 210.8- All receptacle outlets located with in 6' of a sink shall have GFCI protection. Family room receptacle. 422.31- Appliances where receptacle is not accessible lockout shall be inplace. Micro, lock out on 2 garage circuits. Provide access to vacuum recptacle for testing.
|
ELE18-01013
| Final | 6/12/2018 | 6/13/2018 | 6/13/2018 12:01:48 PM | A | FAIL |
|
|
garage code 9224 Phone #: ###-#### Inspection requested via web by Darryn Coburn 110.26- Minimum work space shall be provided for meter base. 30" wide and 36" deep.
|
ELE17-02862
| Electrical Rough-In | 6/13/2018 | 6/13/2018 | 6/13/2018 11:08:44 AM | A | PASS |
|
|
Units 502 , 503 , 504 , 512 , 515 , 516 , 517 , 518 , 519 , elevator equipment room , trash rm , storage rms and 5th floor hallway call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Areas noted walls and fire lids rough in ok cover
|
ELE18-02126
| Final | 6/12/2018 | 6/13/2018 | 6/13/2018 10:30:17 AM | A | FAIL |
|
|
We are requesting a final inspection for this project. Our contact is Larry ###-#### Phone #: ###-#### Inspection requested via web by Larry Looney 250.8(A)(6)- Thread forming machine screws that engage not less than 2 threads in the enclosure shall be used. Permanent service inspection must be approved prior to final inspection. At final shall be labelled and circuit free of shorts.
|
ELE18-01563
| Final | 6/12/2018 | 6/13/2018 | 6/13/2018 9:54:31 AM | A | FAIL |
|
|
Code to get in the door is 12340 Phone #: ###-#### Inspection requested via web by Bud Medcoff 210.8(B)(5)- All single phase receptacles 50 amp or less located with in 6' of a sink shall have GFCI protection. 210.62- At least one 125 volt 15 or 20 amp receptacle outlet shall be installed for show window.
|