FIR18-00447
| INSP-Alarm Testing | 6/13/2018 | 6/13/2018 | 6/13/2018 2:40:27 PM | P | PASS |
|
|
Permit finaled
John Phone #: ###-####
|
BLD17-02777
| FIRE-Final Inspection | 6/13/2018 | 6/13/2018 | 6/13/2018 2:39:52 PM | P | FAIL |
|
|
Remove the deadbolts from doors 102A and 119A and provide with single action, ADA compliant, hardware. Remove the exit sign in the Hallway that directs people to the Service Bays. Provide exit sign at door 102A as per sheet E2.0L. Remove all of the padlock haps.
Please contact Tim Toups at the phone number listed. Phone #: ###-#### Inspection requested via web by Philip Allen
|
NAF18-00006
| INSP-Sprinkler Rough-in | 6/12/2018 | 6/13/2018 | 6/13/2018 1:44:24 PM | A | PASS |
|
|
The piping above the hardlids on the 3rd floor is ok for cover. I also did a preliminary rough-in inspection for all floors. Everything appears ok except for a few items which include branchline restraints will be required for the second floor/south side branchlines and an access panel is needed for the ball drip. Another rough-in inspection will be needed for a cover inspection once the sprinkler drops have been cut.
RICK FRY IS OUR CONTACT Phone #: ###-#### Inspection requested via web by Brad Bettencourt
|
FIR15-00171
| INSP-Final Inspection | 6/12/2018 | 6/13/2018 | 6/13/2018 11:59:23 AM | A | PASS |
|
|
permit finaled
|
FIR17-00522
| INSP-Final Inspection | 6/12/2018 | 6/13/2018 | 6/13/2018 11:47:48 AM | A | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Matthew Lewis
|
FIR18-00309
| INSP-Final Inspection | 6/6/2018 | 6/13/2018 | 6/13/2018 11:34:39 AM | A | FAIL |
|
|
For todays inspection I verified FACP, NAC panels, phone lines, Corridor smoke and Corridor notification spacing. We also set off the notification circuits. I noted that notification will need to be added in two areas. Several devices have been added and another deleted but are shown on the on site as-builts. No initiating devices have been tested. CO detectors may need to be relocated 3' from fan blades Several smoke detectors do need to be relocated more than 3' from diffusers.
Call prior to going Phone #: ###-#### >> Inspection requested via mobile web by Doug
|
NAF18-00049
| INSP-Sprinkler Rough-in/Hydro | 6/12/2018 | 6/13/2018 | 6/13/2018 9:38:25 AM | A | PASS |
|
|
Hydro test for the new piping in the Dining area passed.
Call prior to going Phone #: 2085611337 >> Inspection requested via mobile web by Gabe
|