FIR01-00470
| INSP-Final Inspection | 6/10/2002 | 6/14/2002 | 6/14/2002 12:00:00 AM | A | FAIL |
|
|
see correction notice under permit FIR01-00472 6/14/2002 1:45:44 PM
|
FIR01-00471
| INSP-Final Inspection | 6/10/2002 | 6/14/2002 | 6/14/2002 12:00:00 AM | A | FAIL |
|
|
see correction notice under FIR01-00472 6/14/2002 1:46:03 PM
|
FIR01-00472
| INSP-Final Inspection | 6/10/2002 | 6/14/2002 | 6/14/2002 12:00:00 AM | A | FAIL |
|
|
all sprinkler devices on the first floor need to be tested, 4th floor dry system did not operate correctly, strobes in handicap rooms are mounted to high, place updated map of the fire alarm system at the panel 6/14/2002 1:30:23 PM
|
BLD01-01109
| FIRE-Final Inspection | 6/12/2002 | 6/14/2002 | 6/14/2002 12:00:00 AM | A | PART |
|
|
Doctors office area ok to occupy 6/14/2002 2:05:33 PM
|
BLD02-00308
| FIRE-Final Inspection | 6/13/2002 | 6/14/2002 | 6/14/2002 12:00:00 AM | A | PASS |
|
|
Fire life/safety ok. Structural inspector to verify that sticker is on south door and that the thumbturn/deadbolt has been removed from interior door 6/14/2002 2:46:44 PM
|
MIS02-00131
| FIR-Final | 6/13/2002 | 6/14/2002 | 6/14/2002 12:00:00 AM | A | FAIL |
|
|
Provide "door to remain unlocked sticker" at main exit, provide approved hardware on partition door and rear door, provide fire extinguisher 6/14/2002 3:39:45 PM
|