PLM06-00362
| Final | 6/14/2006 | 6/14/2006 | 6/14/2006 3:53:10 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Steve Spence 1. need main shut off before double check in mechanical room. 2. have double check tested and certified. 3. caulk mop sink at wall and floor. 4. need to provide 120 need hot water limitation for public laves. 5.need open front seat,s on water closet,s. 6. need expansion tank installed on water heater. 7. need to install water heater pan & drain for water heater in overhead 8. need to have occupancy sign off card on job site. left correction notice with general contractor on site
|
PLM05-04309
| Plumbing Rough-in | 6/14/2006 | 6/14/2006 | 6/14/2006 2:38:36 PM | A | PART |
|
|
Scheduled by a contractor via Hello! on 6/14/2006 at 7:12:35 AM. Contact: ###-####. TEST FAILED on third floor under floor DWV on south west side of building need to correct leak and recall when ready
|
PLM06-01998
| Sprinkler (Final) | 6/13/2006 | 6/14/2006 | 6/14/2006 1:28:23 PM | A | PASS |
|
|
###-####
|
PLM06-01596
| Groundwork | 6/13/2006 | 6/14/2006 | 6/14/2006 10:45:39 AM | A | PART |
|
|
tom - Note: top out and groundwork; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ground work and top out for DWV ONLY for pharmacy area test ok
|
PLM06-01997
| Water and/or Sewer | 6/13/2006 | 6/14/2006 | 6/14/2006 10:26:42 AM | A | PART |
|
|
water line only test ok ok to cover
|
PLM06-01807
| Final | 6/13/2006 | 6/14/2006 | 6/14/2006 10:00:07 AM | A | PART |
|
|
ready for final inspection; Phone #: ###-#### Internet Inspection Request from: Jon VanVleet repipe water line in over head and insulate and provide heat tent for final
|
PLM06-01983
| Water and/or Sewer | 6/13/2006 | 6/14/2006 | 6/14/2006 9:58:06 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Scott Wickstrom
|
PLM06-01983
| DOC - Permit Finaled | 6/14/2006 | 6/14/2006 | 6/14/2006 9:57:51 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Scott Wickstrom
|
PLM06-01338
| Groundwork | 6/13/2006 | 6/14/2006 | 6/14/2006 8:59:33 AM | A | PASS |
|
|
BOB; Phone #: ###-#### Internet Inspection Request from: James Stanford
|