Inspections for the day of: Wednesday, June 14, 2006.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-03276 ELE-Aging Inspection6/14/20066/14/20066/14/2006 4:15:43 PM DONE
job suc
ELE05-04540 Final6/14/20066/14/20066/14/2006 4:04:02 PMPPART
Phone #: ###-#### Internet Inspection Request from: Todd Holbrook met contr, needs permanent labels, blank covers, move foreign piping over panel
ELE06-01452 Final6/14/20066/14/20066/14/2006 3:44:18 PMPPART
Phone #: ###-#### Internet Inspection Request from: Todd Holbrook met contr, needs panel labels,blank covers for boxes
ELE06-01702 Electrical Rough-In6/14/20066/14/20066/14/2006 2:45:43 PMPPASS
###-#### - mike Note: gazebo ok to cover , need to see fan box , called contr
ELE06-02174 Electrical Rough-In6/14/20066/14/20066/14/2006 2:04:55 PMPFAIL
butch;Note Underground Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, u/g covered except at ends, he will recall when open per BCC
ELE06-01203 Final6/13/20066/14/20066/14/2006 1:34:32 PMPPART
NEED FINAL INSPECTION ON NEW BUILDING AT 1PM IF POSSIBLE. THANK YOU.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH signed t/o card, left corr notice,BCC 4-05-33(A)(B) motor shall bear listing and labelling marks, rest of job ok
ELE06-02023 Electrical Rough-In6/13/20066/14/20066/14/2006 11:55:03 AMAPASS
shelly; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr made, ric ok
ELE06-02130 Rough-In Permanent Service6/13/20066/14/20066/14/2006 10:39:49 AMAPASS
Scheduled by a contractor via Hello! on 6/13/2006 at 11:45:54 AM. Contact: ###-####. corr made, ric ok, p/s u/g n ok
ELE06-02181 Permanent Service6/13/20066/14/20066/14/2006 9:34:05 AMAPASS
Also inspect trench. Any questions call Jared Keetch.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz u/g ok to cover house to recpts, p/s, u/g, rec, ok
ELE06-02180 Temporary Service6/13/20066/14/20066/14/2006 9:18:51 AMAFAIL
Please contact Pat, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters called, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection,250.24(A) gec shall be connected to gnded conductor terminal, 250.53(G) gnd electrode shall be driven at angle not to exceed 45 degree, BCC job id sticker shall be posted
ELE06-02012 Rough-In Permanent Service6/13/20066/14/20066/14/2006 8:46:51 AMAPASS
Scheduled by a contractor via Hello! on 6/13/2006 at 11:46:38 AM. Contact: ###-####. corr made, ric ok, p/s u/g n ok
ELE06-02165 Final6/13/20066/14/20066/14/2006 8:20:21 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Joseph Zumwalt see t/s ok to final
ELE06-02165 Temporary Service6/14/20066/14/20066/14/2006 8:19:54 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Joseph Zumwalt corr made, t/s u/g n ok
ELE06-02181 Rough-In Permanent Service6/13/20066/14/20066/13/2006 3:22:03 PMACANC
Also inspect trench. Any questions call Jared Keetch.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz Inspection cancelled from web by: Matt Santacruz