Inspections for the day of: Thursday, June 14, 2007.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-02154 Electrical Rough-In6/14/20076/14/20076/14/2007 4:03:12 PMPCANC
soffit inspection ###-#### Internet Inspection Request from: Todd Holbrook called contr to get permits for each space, so that soffit lights can be split among 3 separate spaces as laid out, also said must have some addressing as there is nothing marked, also said that n.e. soffits already covered
ELE07-01138 Final6/14/20076/14/20076/14/2007 3:52:41 PMPPASS
Scheduled by a contractor via Hello! on 6/14/2007 at 8:27:52 AM. Contact: ###-####. called contr to fix panel schedules, ok to final
ELE07-01945 Electrical Rough-In6/14/20076/14/20076/14/2007 2:49:24 PMPPASS
paul; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang ric ok
ELE06-03123 Final6/14/20076/14/20076/14/2007 2:03:42 PMPFAIL
dave ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith told contr, he called for inspection, left corr notice, 406.5 recpt faceplates shall seat against mounting surface, 406.4(D) recpt faces shall be flush with or project from faceplate,406.4 recpts shall be securely fastened in place(laundry), 408.4 circuit directory shall be clear, concise, and explanatory for each circuit and purpose, 210.52(A)(2) 2' wall space shall have recpt behind shower, 110.3(B) listed equip shall be installed per mfgr's instructions(no reverse polarity), 410.8(B) shall provide globe guard for closet light, BCC disposal shall be wired, room count on permit shall be at least 12 rooms
ELE07-02155 Electrical Rough-In6/14/20076/14/20076/14/2007 1:18:11 PMPFAIL
These units are a duplex but are being converted to townhomes in the next couple of weeks. We have done the services as townhomes and will request a service inspection when the conversion is complete. Right now we are just requesting a rough in for cover. Phone #: ###-#### Internet Inspection Request from: Joe Thomas called, left correction notice, nec 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing member, 314.17(C) nm cable shall be stapled within 8" of box
ELE06-02392 Electrical Rough-In6/14/20076/14/20076/14/2007 12:33:25 PMPPASS
randy; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang ok to cover u/g for parking lot lighting
ELE07-00863 ELE-Aging Inspection6/14/20076/14/20076/14/2007 10:57:55 AM NR
looked at sign, looks like they will need to change part
ELE06-02392 Electrical Rough-In6/13/20076/14/20076/14/2007 10:35:59 AMANR
please make inspection as close to 11am as possible. have heavy equip on jobsite and need to cover trench asap. thank you for your help. call Randy Phone #: ###-#### Internet Inspection Request from: Loren Ramsey met contr told to call for pm inspection
ELE07-02135 Final6/13/20076/14/20076/14/2007 10:08:08 AMACANC
Inspect new shed service for irrigation pump & control; trench also for future shop. Phone #: ###-#### Internet Inspection Request from: Lynn Solmon wrong type request, see rip
ELE07-02135 Rough-In Permanent Service6/14/20076/14/20076/14/2007 10:06:54 AMAFAIL
Inspect new shed service for irrigation pump & control; trench also for future shop. Phone #: ###-#### Internet Inspection Request from: Lynn Solmon called left corr notice, nec 352. 26 there shall not be over 360 degree total bend in raceway, 430.102(B) motor disconnect shall be insight of motor, ok to cover u/g up to motor location and towards new shop by shed, told to recall
ELE07-02144 Final6/13/20076/14/20076/14/2007 9:34:22 AMAPASS
dan-- ###-#### cell-- for a hottub ok to final
ELE07-02144 Electrical Rough-In6/14/20076/14/20076/14/2007 9:31:09 AMAPASS
dan-- ###-#### cell-- for a hottub ok to cover u/g
ELE07-02053 Electrical Rough-In6/13/20076/14/20076/14/2007 9:13:22 AMAFAIL
Michael ###-#### called , left corr notice, nec 312.5 abrasion protection shall be provided for all conductors entering enclosures, 250.86 metal enclosures shall be grounded, 250.92(B) bonding jumpers shall be provided around concentrics at service, 314.17(B) jacket shall extend min 1/4" inside box, 310.70(A)(2)(b) at least 1 switched outdoor light shall be provided at man door to garage, BCC all make-up shall be done, minimum 2" riser shall be provided for riser at service, approved guy kit shall be provided, called to install gnd wire in hollow part of ground clamp
ELE07-02150 Electrical Rough-In6/13/20076/14/20076/14/2007 8:18:40 AMAPASS
Brandon ; Phone #: ###-#### Internet Inspection Request from: Darla Downs ric ok
ELE07-02150 Permanent Service6/14/20076/14/20076/14/2007 8:06:30 AMAPASS
Brandon ; Phone #: ###-#### Internet Inspection Request from: Darla Downs p/s u/g n ok