Inspections for the day of: Thursday, June 14, 2007.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00156 INSP-Final Inspection6/13/20076/14/20076/15/2007 10:39:21 AMAPART
FA permit okay for final pending verification of satisfactory state elevator inspection.
FIR07-00453 INSP-Final Inspection6/13/20076/14/20076/14/2007 3:53:57 PMPFAIL
Missing heads in the womens restroom first floor, no coverage provided for the cash room and vault room, overspaced heads on the second floor at a conference room, need all ceiling tile and escutcheons in place prior to final, also need to final the shell and core permit prior to TI finals.
BLD06-03197 FIRE-Final Inspection6/14/20076/14/20076/14/2007 3:49:50 PMPPASS
Fire life safety passed final inspection.
FIR07-00230 INSP-Final Inspection6/14/20076/14/20076/14/2007 3:48:53 PMPPASS
Fire sprinkler permit finaled.
FIR07-00155 INSP-Final Inspection6/14/20076/14/20076/14/2007 3:48:16 PMPPASS
UG fire supply line permit finaled.
FIR07-00155 INSP-Sprinkler Rough-in6/13/20076/14/20076/14/2007 1:25:58 PMPPART
Dry system passed 24 hr. air testing.
FIR07-00023 FIR-Aging Inspection6/14/20076/14/20076/14/2007 11:02:58 AM DONE
Building under construction, work in progress.
FIR07-00422 INSP-Sprinkler Rough-in/Hydro6/13/20076/14/20076/14/2007 10:53:06 AMAPART
Overhead TI modifications are acceptable, permit final pending completion of the ceiling and escutcheon install.
FIR07-00174 INSP-Final Inspection6/13/20076/14/20076/14/2007 10:51:15 AMAFAIL
Required corrections are complete, final pending repair of a leak at one dry SW head in the garage and system pressurization.