Inspections for the day of: Monday, June 14, 2010.
Number of inspections: 22
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-01866 ELE-Aging Inspection6/14/20106/14/20106/18/2010 6:32:19 AM DONE
suc
ELE10-00806 Final6/14/20106/14/20106/15/2010 8:00:32 AMPPASS
final inspection needed Inspection requested from web by: Jon Gleason Phone #: ###-#### ok to final, no card to sign
ELE09-02262 Final6/11/20106/14/20106/14/2010 3:45:45 PMPPASS
Cindy Phone #: ###-#### ok to final
ELE10-01290 Electrical Rough-In6/14/20106/14/20106/14/2010 3:15:56 PMPPASS
pool bonding Inspection requested from web by: Lee VanSchoiack Phone #: ###-#### pool bonding only ok, no u/g done
ELE09-02111 Final6/14/20106/14/20106/14/2010 2:54:20 PMPPASS
Please Call to meet
Desk 3814741
Cell ###-#### Inspection requested from web by: Mark M Phone #: ###-#### ok to final, no card to sign
ELE10-01295 Temporary Service6/14/20106/14/20106/14/2010 2:14:23 PMPFAIL
Phone #: ###-#### called, left correction notice, NEC 312.5 all conductors entering enclosures shall have abrasion protection, 406.8(B) all 15 and 20A outdoor receptacles shall listed weather resistant, BCC shall affix job id sticker, Note: corrections shall be made within 5 working days, fee due
ELE10-01264 Final6/13/20106/14/20106/14/2010 1:42:42 PMPPASS
Please call ahead of time so I can meet with the inspector at the project. I just need a approx. time. Thanks Lynn Waite Inspection requested from web by: Robert Waite Phone #: ###-#### ok to final
ELE10-01275 Electrical Rough-In6/14/20106/14/20106/14/2010 1:09:40 PMPFAIL
pleae inspect grounding electrode Inspection requested from web by: Shaun Kirkman Phone #: ###-#### called, shall install 20' copper in concrete, shall secure copper for pour, shall be done by electrical contractor
ELE10-01229 Electrical Rough-In6/14/20106/14/20106/14/2010 12:31:00 PMPPASS
Underground pipe Inspection requested from web by: Eric Brown Phone #: ###-#### ok to cover sw part building area
ELE10-01287 Conference6/11/20106/14/20106/14/2010 10:40:25 AMAFAIL
Ben Phone #: ###-#### called 2x, no answer, no cars at location, will require another request for conference, could not see posted address
ELE10-01278 Final6/11/20106/14/20106/14/2010 9:59:14 AMAPASS
mark Phone #: ###-#### met contractor, ok to final
ELE10-00478 Final6/14/20106/14/20106/14/2010 9:37:05 AMAPASS
If you cant access the space through the North
entrance they should let you in through the South. Inspection requested from web by: Dan Hardisty Phone #: ###-#### called, ok to final, further work will require new permit, no card to sign sinnce this vanilla finish
ELE10-00724 Electrical Rough-In6/11/20106/14/20106/14/2010 9:07:09 AMAFAIL
CEILING ROUGH COVER INSPECTION READY SERVICE READY ALSO EXCEPT SERVICE WIRE NOT PULLED TO THE IPCO TX YET. Inspection requested from web by: Mike TenHulzen Phone #: ###-#### met electricians, showed them that there shall not be over 4- 90 degree bends in conduit, no open boxes, no open re-bar at service, told to re-call when ready
ELE10-00800 Final6/14/20106/14/20106/14/2010 8:26:11 AMANH
please give me a call half an hour before inspection so that I can insure access. Thanks Shaun ###-#### Inspection requested from web by: Shaun Kirkman Phone #: ###-#### called, left card, fee due
ELE09-01821 Final6/14/20106/14/20106/14/2010 6:27:38 AMAPASS
ok to final
ELE09-01016 Final6/14/20106/14/20106/14/2010 6:23:14 AMAPASS
ok to final
ELE07-03155 ELE-Aging Inspection6/14/20106/14/20106/14/2010 6:21:28 AM DONE
see doc expire
ELE07-03155 DOC - Permit Expired6/14/20106/14/20106/14/2010 6:21:15 AMAPASS
no activity
ELE07-03107 ELE-Aging Inspection6/14/20106/14/20106/14/2010 6:20:16 AM DONE
see doc expire
ELE07-03107 DOC - Permit Expired6/14/20106/14/20106/14/2010 6:20:03 AMAPASS
no activity
ELE07-02464 DOC - Permit Expired6/14/20106/14/20106/14/2010 4:53:12 AMAPASS
no activity
ELE08-01600 DOC - Permit Expired6/14/20106/14/20106/14/2010 4:49:51 AMAPASS
no activity