ESC10-00755
| Aging Inspection | 6/14/2011 | 6/14/2011 | 6/16/2011 2:33:37 PM | | DONE |
|
|
|
ELE11-01099
| Electrical Rough-In | 6/14/2011 | 6/14/2011 | 6/14/2011 3:57:15 PM | P | PASS |
|
|
MIke Phone #: ###-#### track lighting
|
ELE11-00855
| Permanent Service | 6/14/2011 | 6/14/2011 | 6/14/2011 3:56:52 PM | P | PASS |
|
|
p/s u/g ok for meter
|
ELE11-00855
| Rough-In Permanent Service | 6/14/2011 | 6/14/2011 | 6/14/2011 3:56:28 PM | P | PASS |
|
|
Need copy sent to IPCO so power can be turned on. Phone #: ###-#### >> Inspection requested via web by John Edwards
|
ELE11-01172
| Electrical Rough-In | 6/14/2011 | 6/14/2011 | 6/14/2011 3:56:10 PM | P | PASS |
|
|
Electrical Underground Phone #: ###-#### >> Inspection requested via web by Bryan Atkins ok along freeway
|
ELE11-01240
| Electrical Rough-In | 6/14/2011 | 6/14/2011 | 6/14/2011 3:55:41 PM | P | PASS |
|
|
Mike Phone #: ###-#### u/g
|
ELE11-01238
| Permanent Service | 6/14/2011 | 6/14/2011 | 6/14/2011 12:45:59 PM | P | PASS |
|
|
call ###-#### for door code Phone #: ###-#### >> Inspection requested via web by John VanZandt p/s o/h rec. ok
|
ELE11-01238
| Final | 6/14/2011 | 6/14/2011 | 6/14/2011 12:45:35 PM | P | PASS |
|
|
call ###-#### for door code Phone #: ###-#### >> Inspection requested via web by John VanZandt ok
|
ELE11-01106
| Final | 6/8/2011 | 6/14/2011 | 6/14/2011 11:39:13 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Daniel Schaffeld called corr posted 680.26(B)(7)bond soffit vents, crawl space vents, and single gang blank cover 680.22(C)(3) address existing outdoor fixture too close to spa, 220.40 calc p/s it is only 100 amp
|
ELE11-00813
| Final | 6/13/2011 | 6/14/2011 | 6/14/2011 11:35:57 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by David Nelson label panel gfci all recepts 6ft of sink upstairs called
|
ELE11-00252
| ELE-Aging Inspection | 6/14/2011 | 6/14/2011 | 6/14/2011 11:35:02 AM | A | DONE |
|
|
called left message
|
ELE11-01211
| Permanent Service | 6/14/2011 | 6/14/2011 | 6/14/2011 11:34:27 AM | A | PASS |
|
|
p/s u/g new ok
|
ELE11-01211
| Rough-In Permanent Service | 6/13/2011 | 6/14/2011 | 6/14/2011 11:34:00 AM | A | PASS |
|
|
Need to reinspect correction items & ufer grounding electrode Phone #: ###-#### >> Inspection requested via web by Lloyd Looney
|
ELE11-00978
| Final | 6/13/2011 | 6/14/2011 | 6/14/2011 11:33:44 AM | A | PASS |
|
|
(3)Showroom outlets Phone #: ###-#### >> Inspection requested via web by Kevin Burke ok card signed
|