Inspections for the day of: Friday, June 14, 2013.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00175 INSP-Sprinkler Rough-in6/14/20136/14/20136/14/2013 4:27:25 PMPPART
Inspection intended for the remainder of UG fire supply line cover under project related FIR13-00214.
FIR13-00204 INSP-Sprinkler Rough-in6/13/20136/14/20136/14/2013 4:25:44 PMPFAIL
Inspection for sheetrock ceiling cover at the cart storage and cash rooms only- Draft stop above the cart storage area ceiling creates an obstruction to upright sprinkler coverage, noted mixed temp. heads are installed at the cart storage room absent of a specific heat source, missing approved plans on site.
BLD13-01520 FIRE-Final Inspection6/13/20136/14/20136/14/2013 4:21:06 PMPPASS
Life safety inspection completed satisfactory.
BLD13-01504 FIRE-Final Inspection6/13/20136/14/20136/14/2013 4:19:36 PMPPASS
Life safety inspection okay for final pending removal of the manual thumbturn at the main entry/exit door as discussed- To be completed prior to structural final.
BLD13-00660 FIRE-Final Inspection6/13/20136/14/20136/14/2013 4:17:52 PMAPASS
Fire life safety inspection passed. PFE to be posted as discussed.
BLD13-01281 FIRE-Final Inspection6/13/20136/14/20136/14/2013 11:48:13 AMAFAIL
Refer to fire code review notes items number 2, 3, 4, 6 and 7 and the list of general requirements page for details regarding deficiencies including door hardware at the main entry/exit, missing exit signs, fire extinguishers, storage array and racking permit required due to high piled storage over 12'.
BLD13-00792 FIRE-Final Inspection6/13/20136/14/20136/14/2013 11:35:03 AMAPASS
Items noted on correction list are finished. No access to signature card on site at the time of inspection. Fire life safety finaled.
BLD12-02545 FIRE-Final Inspection6/12/20136/14/20136/14/2013 11:31:57 AMAPASS
Scope of work completed, life safety passed.
BLD13-01231 FIRE-Final Inspection6/13/20136/14/20136/14/2013 11:28:58 AMAPASS
Previous correction items verified for completion. Fire life safety finaled. New openings at the south side are finished- doors and landings not yet installed.