ELE12-02995
| ELE-Aging Inspection | 6/14/2016 | 6/14/2016 | 6/15/2016 3:44:43 PM | | PASS |
|
|
Waiting on owner
|
ELE16-00925
| Electrical Rough-In | 6/13/2016 | 6/14/2016 | 6/14/2016 3:47:32 PM | P | PASS |
|
|
Lee-would like late pm if poss Phone #: ###-#### Phase 2 entry walls rough in ok cover
|
ELE16-01874
| Electrical Rough-In | 6/13/2016 | 6/14/2016 | 6/14/2016 3:19:50 PM | P | PASS |
|
|
Please inspect underground for cover. Phone #: ###-#### Inspection requested via web by Spencer McLean Underground for verizon meter from in ground box to south fence rough in ok cover
|
ELE16-01483
| Conference | 6/13/2016 | 6/14/2016 | 6/14/2016 2:38:25 PM | P | DONE |
|
|
Please contact Greg 30 min prior to arrival. This is for a consultation. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker Discussed the ampacity of feeders from basement to each unit. Quoted NEC 310.15(A)(2)exeption, if less than 10' or 10% of circuit length is enclosed by thermal insulation adjustment factor of using 60 degree column shall not apply. General contractor to assist with uninsulated path to help with costs of wiring.
|
ELE16-01875
| Temporary Service | 6/14/2016 | 6/14/2016 | 6/14/2016 1:53:06 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Therrin Robertson t/s u/g n ok
|
ELE16-01653
| Electrical Rough-In | 6/14/2016 | 6/14/2016 | 6/14/2016 12:59:59 PM | P | PASS |
|
|
2nd floor ceiling rough-in Phone #: ###-#### Inspection requested via web by JENNY EMEL 2nd floor corridor grid rough in ok cover
|
ELE16-00089
| Electrical Rough-In | 6/13/2016 | 6/14/2016 | 6/14/2016 12:40:23 PM | P | PASS |
|
|
Call Bob for inspection of 5th floor IT room exterior wall. Phone #: ###-#### Inspection requested via web by Rafael Castillo As noted and marked on print wall rough in ok cover
|
ELE15-03901
| Electrical Rough-In | 6/13/2016 | 6/14/2016 | 6/14/2016 12:34:11 PM | A | PASS |
|
|
Call Pierce for ceiling inspection of 7th floor server room area. Phone #: ###-#### Inspection requested via web by Rafael Castillo 7th floor server room center grid tiles ok to install for equipment.
|
ELE15-01617
| Electrical Rough-In | 6/13/2016 | 6/14/2016 | 6/14/2016 11:13:56 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton 1st floor entry soffits and east fireplace wall, 4th floor student desk soffit and bathroom hardlids rough in ok cover
|
ELE16-01870
| Electrical Rough-In | 6/13/2016 | 6/14/2016 | 6/14/2016 10:32:54 AM | A | PASS |
|
|
Bonding Inspection Phone #: ###-#### Inspection requested via web by Louis Keller Stubs an on all 4 corners, light, stub for cover rough in ok cover
|
ELE16-01334
| Final | 6/13/2016 | 6/14/2016 | 6/14/2016 10:02:41 AM | A | FAIL |
|
|
Good morning, This will be a final for this permit please. Contact is David Joseph ###-####. Please give him a call if you have any questions as he will not be o the job site. Thank you and have a super day! Phone #: ###-#### Inspection requested via web by Laura Longshaw 210.8(B)-All 120 volt 20 amp receptacle outlets located within 6' of a sink or basin shall have GFCI protection. 110.3- Twin breaker modified to be installed in a panel not listed for twin breakers.
|
ELE16-01264
| Final | 6/14/2016 | 6/14/2016 | 6/14/2016 9:38:48 AM | A | PASS |
|
|
CODE 1234 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
|
ESC16-00306
| Random Inspection | 6/14/2016 | 6/14/2016 | 6/14/2016 9:38:15 AM | P | PASS |
|
|
Landscape not started yet, clean job site
|
ELE16-01154
| Final | 6/14/2016 | 6/14/2016 | 6/14/2016 9:24:42 AM | A | PASS |
|
|
CODE 1234 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
|
ESC16-00280
| Random Inspection | 6/14/2016 | 6/14/2016 | 6/14/2016 9:23:55 AM | P | PASS |
|
|
Front landscape complete clean job site
|
ELE16-00901
| Electrical Rough-In | 6/13/2016 | 6/14/2016 | 6/14/2016 8:26:18 AM | A | PASS |
|
|
Dan ###-#### phase 2 CT wall rough in ok cover
|
ELE16-00901
| Electrical Rough-In | 6/13/2016 | 6/14/2016 | 6/13/2016 4:14:46 PM | A | CANC |
|
|
Dan ###-####
|