Inspections for the day of: Tuesday, June 14, 2016.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-02740 Final6/14/20166/14/20166/14/2016 3:44:40 PMPPART
Seth Phone #: ###-#### Temporary occupancy for 4th floor to move build-in furniture into dwelling units only.
ELE16-01848 Final6/14/20166/14/20166/14/2016 3:15:44 PMPNH
Phone #: ###-#### Inspection requested via web by Matthew White No access, nobody home.
ELE16-00129 Final6/14/20166/14/20166/14/2016 2:32:51 PMPPASS
Phone #: ###-#### Inspection requested via web by kendall bender Parking lot lighting and Shell only, final ok
ELE16-00390 Final6/13/20166/14/20166/14/2016 2:15:08 PMPFAIL
Doug Phone #: ###-#### NEC 210.8(B)(2) All 15 and 20 ampere 120 volt receptacle within 6ft of a sink requires GCFI protection. NEC 406.8(9)(B)(1) Receptacles installed in wet locations shall be listed weather-resistant type.NEC 406.12 Child care facilities require tamper-resistant receptacles. NEC 422.52 Electric drinking fountains require GFCI protection
ELE16-01220 Final6/13/20166/14/20166/14/2016 12:28:32 PMAPASS
Call Steve when in route if possible; Obtain visitors pass from front desk. Phone #: ###-#### Inspection requested via web by Steve McCloy UL Listed cubicles final ok
ELE15-04016 Final6/13/20166/14/20166/14/2016 12:24:39 PMAPASS
Phone #: ###-#### Inspection requested via web by mike brown final ok
ELE16-01713 Final6/13/20166/14/20166/14/2016 10:36:52 AMAPASS
Phone #: 2088694676 >> Inspection requested via mobile web by Barry Spencer final ok
ELE16-01450 Final6/13/20166/14/20166/14/2016 10:08:48 AMAPASS
Meter cover with passthroughs is on and ready Phone #: ###-#### Inspection requested via web by Cindie Swaim correction done, final ok
ELE16-01646 Electrical Rough-In6/14/20166/14/20166/14/2016 9:33:00 AMAPASS
Phone #: 2088694676 >> Inspection requested via mobile web by Barry Spencer ETL Listed PV equipment rough-in ok
ELE15-01436 Final6/10/20166/14/20166/14/2016 9:01:47 AMAPASS
would like call ahead; Biff Phone #: ###-#### final ok