BLD15-03583
| FIRE-Final Inspection | 6/10/2016 | 6/14/2016 | 6/14/2016 2:35:05 PM | P | FAIL |
|
|
Fire sprinkler inspection is complete, emergency egress lighting inspection complete, no fire extinguishers due to shell being unoccupied space until tenant improvements happen. Fire alarm inspection partially complete, in-duct smoke detectors could not be tested in HVAC units due to no power supply connected to HVAC units. The HVAC untis need to have power to be tested for unti shutdown or the genereal contractor needs documentation from the city supporting the HVAC units being disconnected and in-duct detection being INOP. Building fire protection is with a wet pipe fire sprinkler system so interior space needs to be a conditioned space to prevent freezing.
|
BLD15-03584
| FIRE-Final Inspection | 6/10/2016 | 6/14/2016 | 6/14/2016 2:34:08 PM | P | FAIL |
|
|
Fire sprinkler inspection is complete, emergency egress lighting inspection complete, no fire extinguishers due to shell being unoccupied space until tenant improvements happen. Fire alarm inspection partially complete, in-duct smoke detectors could not be tested in HVAC units due to no power supply connected to HVAC units. The HVAC untis need to have power to be tested for unti shutdown or the genereal contractor needs documentation from the city supporting the HVAC units being disconnected and in-duct detection being INOP. Building fire protection is with a wet pipe fire sprinkler system so interior space needs to be a conditioned space to prevent freezing.
|
FIR16-00132
| INSP-Final Inspection | 6/13/2016 | 6/14/2016 | 6/14/2016 2:25:08 PM | P | PART |
|
|
Fire alarm inspection partially complete, tested/inspected waterflow, tampers, smoke detector above fire panel and pull station, HVAC units are over 2000cfm so HVAC untis require duct detectors with unit shutdown (induct detectors are shown on city approved drawings), HVAC units do not have power connected so duct detectors were INOP at time of inspection. Duct detectors need to be in operation or general contractor needs to have documentation from the city supporting the duct detectors being INOP.
|
FIR16-00137
| INSP-Final Inspection | 6/13/2016 | 6/14/2016 | 6/14/2016 2:23:22 PM | P | PART |
|
|
Fire alarm inspection partially complete, tested/inspected waterflow, tampers, smoke detector above fire panel and pull station, HVAC units are over 2000cfm so HVAC untis require duct detectors with unit shutdown, HVAC units do not have power connected so duct detectors were INOP at time of inspection. Duct detectors need to be in operation or general contractor needs to have documentation from the city supporting the duct detectors being INOP.
|
FIR16-00375
| INSP-Final Inspection | 6/13/2016 | 6/14/2016 | 6/14/2016 2:15:41 PM | P | PART |
|
|
Final fire alarm communicator inspection passed/complete
|
FIR16-00382
| INSP-Final Inspection | 6/13/2016 | 6/14/2016 | 6/14/2016 2:14:39 PM | P | PASS |
|
|
Final fire alarm communicator inspection passed/complete
|
FIR16-00135
| INSP-Final Inspection | 6/13/2016 | 6/14/2016 | 6/14/2016 2:13:45 PM | P | PASS |
|
|
Final underground supply inspection passed/complete
|
FIR16-00106
| INSP-Final Inspection | 6/13/2016 | 6/14/2016 | 6/14/2016 2:12:51 PM | P | PASS |
|
|
Final fire sprinkler inspection passed/complete
|
FIR16-00049
| INSP-Final Inspection | 6/13/2016 | 6/14/2016 | 6/14/2016 2:11:58 PM | P | PASS |
|
|
Final fire sprinkler inspection passed/complete
|
BLD16-01323
| FIRE-Final Inspection | 6/14/2016 | 6/14/2016 | 6/14/2016 11:04:46 AM | P | PASS |
|
|
Fire alarm panel shows system is normal, final life fire safety inspection passed/complete.
|
FIR16-00188
| INSP-Sprinkler Rough-in | 6/13/2016 | 6/14/2016 | 6/14/2016 10:36:22 AM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping complete, overhead fire sprinkler piping approved for cover.
|
FIR16-00103
| INSP-Supply line flush | 6/13/2016 | 6/14/2016 | 6/14/2016 9:51:44 AM | A | DONE |
|
|
Underground main line flush complete
|
FIR16-00312
| INSP-Final Inspection | 6/13/2016 | 6/14/2016 | 6/14/2016 8:27:23 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete
|
FIR16-00049
| INSP-Final Inspection | 6/13/2016 | 6/14/2016 | 6/13/2016 1:18:48 PM | A | CANC |
|
|
Please call Jake when you are heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|
FIR16-00135
| INSP-Final Inspection | 6/13/2016 | 6/14/2016 | 6/13/2016 1:18:45 PM | A | CANC |
|
|
Please call Jake when you are heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|
FIR16-00106
| INSP-Final Inspection | 6/13/2016 | 6/14/2016 | 6/13/2016 1:18:43 PM | A | CANC |
|
|
Please call Jake when you are heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|