Inspections for the day of: Tuesday, June 14, 2016.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD15-03583 FIRE-Final Inspection6/10/20166/14/20166/14/2016 2:35:05 PMPFAIL
Fire sprinkler inspection is complete, emergency egress lighting inspection complete, no fire extinguishers due to shell being unoccupied space until tenant improvements happen. Fire alarm inspection partially complete, in-duct smoke detectors could not be tested in HVAC units due to no power supply connected to HVAC units. The HVAC untis need to have power to be tested for unti shutdown or the genereal contractor needs documentation from the city supporting the HVAC units being disconnected and in-duct detection being INOP. Building fire protection is with a wet pipe fire sprinkler system so interior space needs to be a conditioned space to prevent freezing.
BLD15-03584 FIRE-Final Inspection6/10/20166/14/20166/14/2016 2:34:08 PMPFAIL
Fire sprinkler inspection is complete, emergency egress lighting inspection complete, no fire extinguishers due to shell being unoccupied space until tenant improvements happen. Fire alarm inspection partially complete, in-duct smoke detectors could not be tested in HVAC units due to no power supply connected to HVAC units. The HVAC untis need to have power to be tested for unti shutdown or the genereal contractor needs documentation from the city supporting the HVAC units being disconnected and in-duct detection being INOP. Building fire protection is with a wet pipe fire sprinkler system so interior space needs to be a conditioned space to prevent freezing.
FIR16-00132 INSP-Final Inspection6/13/20166/14/20166/14/2016 2:25:08 PMPPART
Fire alarm inspection partially complete, tested/inspected waterflow, tampers, smoke detector above fire panel and pull station, HVAC units are over 2000cfm so HVAC untis require duct detectors with unit shutdown (induct detectors are shown on city approved drawings), HVAC units do not have power connected so duct detectors were INOP at time of inspection. Duct detectors need to be in operation or general contractor needs to have documentation from the city supporting the duct detectors being INOP.
FIR16-00137 INSP-Final Inspection6/13/20166/14/20166/14/2016 2:23:22 PMPPART
Fire alarm inspection partially complete, tested/inspected waterflow, tampers, smoke detector above fire panel and pull station, HVAC units are over 2000cfm so HVAC untis require duct detectors with unit shutdown, HVAC units do not have power connected so duct detectors were INOP at time of inspection. Duct detectors need to be in operation or general contractor needs to have documentation from the city supporting the duct detectors being INOP.
FIR16-00375 INSP-Final Inspection6/13/20166/14/20166/14/2016 2:15:41 PMPPART
Final fire alarm communicator inspection passed/complete
FIR16-00382 INSP-Final Inspection6/13/20166/14/20166/14/2016 2:14:39 PMPPASS
Final fire alarm communicator inspection passed/complete
FIR16-00135 INSP-Final Inspection6/13/20166/14/20166/14/2016 2:13:45 PMPPASS
Final underground supply inspection passed/complete
FIR16-00106 INSP-Final Inspection6/13/20166/14/20166/14/2016 2:12:51 PMPPASS
Final fire sprinkler inspection passed/complete
FIR16-00049 INSP-Final Inspection6/13/20166/14/20166/14/2016 2:11:58 PMPPASS
Final fire sprinkler inspection passed/complete
BLD16-01323 FIRE-Final Inspection6/14/20166/14/20166/14/2016 11:04:46 AMPPASS
Fire alarm panel shows system is normal, final life fire safety inspection passed/complete.
FIR16-00188 INSP-Sprinkler Rough-in6/13/20166/14/20166/14/2016 10:36:22 AMPPASS
Rough to cover inspection for overhead fire sprinkler piping complete, overhead fire sprinkler piping approved for cover.
FIR16-00103 INSP-Supply line flush6/13/20166/14/20166/14/2016 9:51:44 AMADONE
Underground main line flush complete
FIR16-00312 INSP-Final Inspection6/13/20166/14/20166/14/2016 8:27:23 AMAPASS
Final fire alarm inspection passed/complete
FIR16-00049 INSP-Final Inspection6/13/20166/14/20166/13/2016 1:18:48 PMACANC
Please call Jake when you are heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
FIR16-00135 INSP-Final Inspection6/13/20166/14/20166/13/2016 1:18:45 PMACANC
Please call Jake when you are heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
FIR16-00106 INSP-Final Inspection6/13/20166/14/20166/13/2016 1:18:43 PMACANC
Please call Jake when you are heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello