Inspections for the day of: Wednesday, June 14, 2017.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-03342 Rough-In Permanent Service6/12/20176/14/20176/14/2017 1:38:38 PMPFAIL
Phone #: ###-#### Inspection requested via web by cris flores
Grounds and neutrals shall be seperated
Group disc
ELE17-01695 Final6/7/20176/14/20176/14/2017 1:37:16 PMPCANC
There will be guys there. If you have any questions please call Jake ###-#### Thanks!! Phone #: ###-#### Inspection requested via web by Clay Morgan
No final at this time
ELE17-01695 Permanent Service6/7/20176/14/20176/14/2017 1:36:10 PMPPASS
There will be guys there working. If you have any questions please call Jake ###-#### Thanks!! Phone #: ###-#### Inspection requested via web by Clay Morgan
p/s o/h rec ok
ELE17-00748 Electrical Rough-In6/14/20176/14/20176/14/2017 12:53:35 PMPPASS
Justin Hamby Phone #: ###-#### Inspection requested via web by Laurie Hoelscher
Sign final ok
ELE17-01796 Final6/13/20176/14/20176/14/2017 10:55:42 AMAPASS
Please contact Allison Bataineh at ###-#### for property access between 8am and noon Phone #: ###-#### Inspection requested via web by jamie berg
FInal for a/c and furnace ok
ELE17-01755 Electrical Rough-In6/13/20176/14/20176/14/2017 9:31:19 AMAPASS
Thanks Phone #: ###-#### Inspection requested via web by Tom Jenkins
Kitchen prep areas hard lid ceilngs only ok cover
ELE17-01631 Electrical Rough-In6/14/20176/14/20176/14/2017 9:13:10 AMACANC
Please call before heading to location so that I can make sure access to the building is available. Phone #: ###-#### Inspection requested via web by Spencer McLean
Needed conference
ELE17-01631 Conference6/14/20176/14/20176/14/2017 9:13:04 AMPDONE
Please call before heading to location so that I can make sure access to the building is available. Phone #: ###-#### Inspection requested via web by Spencer McLean
Discussed what areas as workis to be done and will bring what is replace. Main work will be done in kitchen and circuits will be brought to code and as well as placement of receptacles, living room will be fixed from open neutral and GFCI protection on open grounded circuits. Exposed romex above remote panel will be protected from physical damage.
ELE16-03914 Final6/13/20176/14/20176/14/2017 8:22:25 AMAFAIL
Phone #: ###-#### Inspection requested via web by michael hunt
210.12 All receptacles shall have AFCI protection including smokes
Finish mini split units