ELE18-01720
| Electrical Rough-In | 6/14/2018 | 6/14/2018 | 6/14/2018 2:10:51 PM | P | PASS |
|
|
Mark--rough in for underground cover Phone #: ###-#### Underground from gear to distibution panels and stubs to the west rough in ok cover
|
ELE18-01362
| Final | 6/14/2018 | 6/14/2018 | 6/14/2018 1:41:40 PM | P | FAIL |
|
|
access code 3535 Phone #: ###-#### Inspection requested via web by Paula Gratiot 110.3- Entry hall 3way, 4way, 3way will not operate with 4 way in either position. 110.3- Christmas GFCI will not trip when tested. 210.12- Office has a closet with a clothes rod and shall have AFCI protection.
|
ELE18-00727
| Electrical Rough-In | 6/14/2018 | 6/14/2018 | 6/14/2018 12:52:46 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Tom Jenkins Menu board bases rough in ok cover
|
ELE18-02198
| Temporary Service | 6/13/2018 | 6/14/2018 | 6/14/2018 12:10:15 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
|
ELE18-02195
| Temporary Service | 6/13/2018 | 6/14/2018 | 6/14/2018 12:09:23 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
|
ELE18-00891
| Final | 6/13/2018 | 6/14/2018 | 6/14/2018 11:37:14 AM | A | FAIL |
|
|
Call Jared ###-#### for access. If you have any questions please feel free to contact Alan ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan 210.52- Kitchen Counter top 12" or wider shall have a receptacle outlet installed ldft of range. 314.17(C)- NM cable sheath shall enter box a minimum of 1/4". Refer receptacle moved to right of original location. Verbal with contact.
|
ELE17-02862
| Electrical Rough-In | 6/14/2018 | 6/14/2018 | 6/14/2018 11:04:49 AM | A | PASS |
|
|
Units 513 , 514 and 5th floor stairs #1 and #2 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Areas noted and elevator dog house stub rough in ok cover. Left green tag on electrical office door.
|
ELE18-01764
| Final | 6/13/2018 | 6/14/2018 | 6/13/2018 1:15:29 PM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Dean Gernaat Inspection cancelled from web by: Dean Gernaat
|
ELE18-01764
| Final | 6/13/2018 | 6/14/2018 | 6/13/2018 9:24:22 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Dean Gernaat Job not complete, bar not done, still hanging lights. Spoke with crew on site. Will recall when ready.
|