Inspections for the day of: Thursday, June 14, 2018.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-01720 Electrical Rough-In6/14/20186/14/20186/14/2018 2:10:51 PMPPASS
Mark--rough in for underground cover Phone #: ###-####
Underground from gear to distibution panels and stubs to the west rough in ok cover
ELE18-01362 Final6/14/20186/14/20186/14/2018 1:41:40 PMPFAIL
access code 3535 Phone #: ###-#### Inspection requested via web by Paula Gratiot
110.3- Entry hall 3way, 4way, 3way will not operate with 4 way in either position.
110.3- Christmas GFCI will not trip when tested.
210.12- Office has a closet with a clothes rod and shall have AFCI protection.
ELE18-00727 Electrical Rough-In6/14/20186/14/20186/14/2018 12:52:46 PMPPASS
Phone #: ###-#### Inspection requested via web by Tom Jenkins
Menu board bases rough in ok cover
ELE18-02198 Temporary Service6/13/20186/14/20186/14/2018 12:10:15 PMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
ELE18-02195 Temporary Service6/13/20186/14/20186/14/2018 12:09:23 PMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
ELE18-00891 Final6/13/20186/14/20186/14/2018 11:37:14 AMAFAIL
Call Jared ###-#### for access. If you have any questions please feel free to contact Alan ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan
210.52- Kitchen Counter top 12" or wider shall have a receptacle outlet installed ldft of range.
314.17(C)- NM cable sheath shall enter box a minimum of 1/4". Refer receptacle moved to right of original location.
Verbal with contact.
ELE17-02862 Electrical Rough-In6/14/20186/14/20186/14/2018 11:04:49 AMAPASS
Units 513 , 514 and 5th floor stairs #1 and #2 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Areas noted and elevator dog house stub rough in ok cover. Left green tag on electrical office door.
ELE18-01764 Final6/13/20186/14/20186/13/2018 1:15:29 PMACANC
Phone #: ###-#### >> Inspection requested via web by Dean Gernaat Inspection cancelled from web by: Dean Gernaat
ELE18-01764 Final6/13/20186/14/20186/13/2018 9:24:22 AMAFAIL
Phone #: ###-#### Inspection requested via web by Dean Gernaat
Job not complete, bar not done, still hanging lights. Spoke with crew on site. Will recall when ready.