Inspections for the day of: Thursday, June 14, 2018.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00094 INSP-Alarm Testing6/14/20186/14/20186/14/2018 2:56:36 PMPFAIL
Plan mods are needed showing the changes which include addresses and fire sprinkler device layout. I tried testing today but when we started there were 79 troubles on the panel. When test for sprinkler alarms the panel started functioning incorrectly. I ended the inspection. Project is not ready for inspection.

Rand Phone #: ###-####
FIR17-00522 INSP-Final Inspection6/13/20186/14/20186/14/2018 2:54:28 PMAFAIL
Waiting on the project related fire alarm permit so that the interconnections can be tested. Forward flush passed. Need to inspect the Smokers Canopy.

Phone #: ###-#### Inspection requested via web by Matthew Lewis
FIR18-00327 INSP-Sprinkler Rough-in/Hydro6/13/20186/14/20186/14/2018 12:42:15 PMAPASS
Rough in for the dry system and hydro on dry system passed. Also the two new wet system branchlines passed.

Phone #: ###-#### Inspection requested via web by Sam Ball
BLD17-04274 FIRE-Final Inspection6/13/20186/14/20186/14/2018 8:45:33 AMAFAIL
Provide exit discharge lights per the approved plans. Mount the two fire extinguishers in the DIning Area and provide an additional one in the back corridor. Provide the two occupant load signs.

Phone #: ###-#### Inspection requested via web by Don Walker
FIR18-00093 INSP-Final Inspection6/11/20186/14/20186/14/2018 8:43:10 AMAPASS
permit finaled
BLD18-00221 FIRE-Final Inspection6/13/20186/14/20186/14/2018 7:55:10 AMAPASS
Life safety passed

Cecil Phone #: ###-####