FIR18-00094
| INSP-Alarm Testing | 6/14/2018 | 6/14/2018 | 6/14/2018 2:56:36 PM | P | FAIL |
|
|
Plan mods are needed showing the changes which include addresses and fire sprinkler device layout. I tried testing today but when we started there were 79 troubles on the panel. When test for sprinkler alarms the panel started functioning incorrectly. I ended the inspection. Project is not ready for inspection.
Rand Phone #: ###-####
|
FIR17-00522
| INSP-Final Inspection | 6/13/2018 | 6/14/2018 | 6/14/2018 2:54:28 PM | A | FAIL |
|
|
Waiting on the project related fire alarm permit so that the interconnections can be tested. Forward flush passed. Need to inspect the Smokers Canopy.
Phone #: ###-#### Inspection requested via web by Matthew Lewis
|
FIR18-00327
| INSP-Sprinkler Rough-in/Hydro | 6/13/2018 | 6/14/2018 | 6/14/2018 12:42:15 PM | A | PASS |
|
|
Rough in for the dry system and hydro on dry system passed. Also the two new wet system branchlines passed.
Phone #: ###-#### Inspection requested via web by Sam Ball
|
BLD17-04274
| FIRE-Final Inspection | 6/13/2018 | 6/14/2018 | 6/14/2018 8:45:33 AM | A | FAIL |
|
|
Provide exit discharge lights per the approved plans. Mount the two fire extinguishers in the DIning Area and provide an additional one in the back corridor. Provide the two occupant load signs.
Phone #: ###-#### Inspection requested via web by Don Walker
|
FIR18-00093
| INSP-Final Inspection | 6/11/2018 | 6/14/2018 | 6/14/2018 8:43:10 AM | A | PASS |
|
|
permit finaled
|
BLD18-00221
| FIRE-Final Inspection | 6/13/2018 | 6/14/2018 | 6/14/2018 7:55:10 AM | A | PASS |
|
|
Life safety passed
Cecil Phone #: ###-####
|