FIR04-00143
| FIR-Aging Inspection | 6/15/2004 | 6/15/2004 | 6/15/2004 12:00:00 AM | | NR |
|
|
Installation is nearly complete. Alarm contractor is searching for a tamper switch for a sprinkler valve. 6/15/2004 11:31:35 AM
|
FIR04-00346
| INSP-Final Inspection | 6/14/2004 | 6/15/2004 | 6/15/2004 12:00:00 AM | A | PASS |
|
|
Hood suppression system operated correctly. The suppression system is not connected to the alarm system yet. 6/15/2004 11:30:43 AM
|
FIR03-00770
| INSP-Final Inspection | 6/15/2004 | 6/15/2004 | 6/15/2004 12:00:00 AM | P | FAIL |
|
|
NAC panel, circuit 3, on the second floor is in trouble (a/v's don't work). Need to verify batteries, end of line voltage drop and trouble signals on 2nd floor nac panel. Need to test heat detectors in attic. 6/15/2004 2:39:34 PM
|
FIR03-00453
| INSP-Final Inspection | 6/15/2004 | 6/15/2004 | 6/15/2004 12:00:00 AM | P | PART |
|
|
Inspection was for the assisted living area on the southwest corner of the building. All items tested except for the sprinkler flow alarms and the PIV. Some items need corrected. See city approved plans for specific items. 6/15/2004 4:08:11 PM
|