Inspections for the day of: Tuesday, June 15, 2004.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00143 FIR-Aging Inspection6/15/20046/15/20046/15/2004 12:00:00 AM NR
Installation is nearly complete. Alarm contractor is searching for a tamper switch for a sprinkler valve. 6/15/2004 11:31:35 AM
FIR04-00346 INSP-Final Inspection6/14/20046/15/20046/15/2004 12:00:00 AMAPASS
Hood suppression system operated correctly. The suppression system is not connected to the alarm system yet. 6/15/2004 11:30:43 AM
FIR03-00770 INSP-Final Inspection6/15/20046/15/20046/15/2004 12:00:00 AMPFAIL
NAC panel, circuit 3, on the second floor is in trouble (a/v's don't work). Need to verify batteries, end of line voltage drop and trouble signals on 2nd floor nac panel. Need to test heat detectors in attic. 6/15/2004 2:39:34 PM
FIR03-00453 INSP-Final Inspection6/15/20046/15/20046/15/2004 12:00:00 AMPPART
Inspection was for the assisted living area on the southwest corner of the building. All items tested except for the sprinkler flow alarms and the PIV. Some items need corrected. See city approved plans for specific items. 6/15/2004 4:08:11 PM