Inspections for the day of: Wednesday, June 15, 2005.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00113 FIR-Aging Inspection6/15/20056/15/20056/16/2005 8:38:57 AM DONE
I spoke to Thad about job status. He is to investigate. Followup inspection setup for the 29th
BLD05-00057 FIRE-Conference6/15/20056/15/20056/15/2005 4:27:11 PMPDONE
###-####; I clarified door hardware requirements with contractor.
FIR05-00124 FIR-Aging Inspection6/15/20056/15/20056/15/2005 2:51:17 PM DONE
Work in progress
BLD04-01051 FIRE-Final Inspection6/14/20056/15/20056/15/2005 2:50:49 PMAFAIL
bill; Phone #: ###-#### Remove thumbturn locks from east exit doors, Provide "Door to remain unlocked when building is occupied" at both of the east exit doors, test duct smoke detectors and provide with approved remote annunciators, provide address numbers viewable from Fairview. Fixed seating is not allowed per shell permit review comments.
BLD05-00600 FIRE-Final Inspection6/14/20056/15/20056/15/2005 11:27:02 AMAFAIL
The correct remote annunciators have been installed and they operate correctly but when the duct detectors goes into alarm they do not shut down the hvac units.