FIR02-00113
| FIR-Aging Inspection | 6/15/2005 | 6/15/2005 | 6/16/2005 8:38:57 AM | | DONE |
|
|
I spoke to Thad about job status. He is to investigate. Followup inspection setup for the 29th
|
BLD05-00057
| FIRE-Conference | 6/15/2005 | 6/15/2005 | 6/15/2005 4:27:11 PM | P | DONE |
|
|
###-####; I clarified door hardware requirements with contractor.
|
FIR05-00124
| FIR-Aging Inspection | 6/15/2005 | 6/15/2005 | 6/15/2005 2:51:17 PM | | DONE |
|
|
Work in progress
|
BLD04-01051
| FIRE-Final Inspection | 6/14/2005 | 6/15/2005 | 6/15/2005 2:50:49 PM | A | FAIL |
|
|
bill; Phone #: ###-#### Remove thumbturn locks from east exit doors, Provide "Door to remain unlocked when building is occupied" at both of the east exit doors, test duct smoke detectors and provide with approved remote annunciators, provide address numbers viewable from Fairview. Fixed seating is not allowed per shell permit review comments.
|
BLD05-00600
| FIRE-Final Inspection | 6/14/2005 | 6/15/2005 | 6/15/2005 11:27:02 AM | A | FAIL |
|
|
The correct remote annunciators have been installed and they operate correctly but when the duct detectors goes into alarm they do not shut down the hvac units.
|