Inspections for the day of: Friday, June 15, 2007.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-01428 Final6/15/20076/15/20076/15/2007 3:36:13 PMPPASS
CHARLES; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to final
ELE07-01144 Electrical Rough-In6/15/20076/15/20076/15/2007 2:51:05 PMPPASS
Underground
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton ok to cover u/g bldg to parking lot light
ELE07-02173 Permanent Service6/15/20076/15/20076/15/2007 2:12:02 PMPFAIL
randy ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called left corr notice, nec 352.30 & 358.30 conduit shall be supported within 3' of panel, 110.12(C) there shall be no damaged parts-panel cover hinge, grounding electrode conductor, 250.52(A) shall use metal water pipe for gnd electrode,210.53(D)(2) shall supplement electrode with 2 ground rods, 210.53(G) grd rods shall be driven 8' into ground, upper end flush with or below ground, 110.3(B) shall use listed gnd clamps,BCC no violations shall be retained
ELE07-01873 Electrical Rough-In6/14/20076/15/20076/15/2007 1:25:14 PMPFAIL
tom; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang met owner, BCC all make-up shall be done, nec 250.86 shall ground metal boxes, 210.70(A)(2) shall provide exit lite at mandoor in garage
ELE07-02098 Electrical Rough-In6/15/20076/15/20076/15/2007 12:30:16 PMPCANC
Ready for Re-inspection
Ready for final
call Dan with any questions Phone #: ###-#### Internet Inspection Request from: Dan Mitchell called , see permit ele07-02113, this permit should be cancelled, wrong address
ELE07-02113 Electrical Rough-In6/15/20076/15/20076/15/2007 12:29:17 PMPPASS
ok to cover clg, see permit ele07-02098 for first inspection with wrong address, will call for final ltr
ELE07-02154 Final6/15/20076/15/20076/15/2007 10:30:23 AMAPASS
soffit rough in ###-#### Internet Inspection Request from: Todd Holbrook ok to cover soffits only
ELE07-02170 Final6/15/20076/15/20076/15/2007 10:13:12 AMAPASS
soffit rough in ###-#### Internet Inspection Request from: Todd Holbrook soffit only ok to cover
ELE07-02131 Electrical Rough-In6/14/20076/15/20076/15/2007 9:47:30 AMAPASS
judith; Phone #: ###-#### corrections made, ric ok
ELE07-00968 Conference6/14/20076/15/20076/15/2007 9:16:01 AMADONE
julie; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles talked about ckt extension, when to call for ri
ELE07-00592 Final6/15/20076/15/20076/15/2007 8:59:15 AMAPASS
Call Dave if this inspection fails! Thank you and have a great weekend!
Kathy Phone #: ###-#### Internet Inspection Request from: KATHY WEIL see permit ele07-02172, for final info.
ELE07-02172 Final6/15/20076/15/20076/15/2007 8:41:55 AMAPASS
ri and p/s done under permit # ele07-00592, which was t/s, told contractor to update, but instead pulled new permit, ok to final
ELE07-02135 Final6/14/20076/15/20076/15/2007 7:50:06 AMAPASS
Inspection for correction of motor disconnect. Thank you Bob!! Phone #: ###-#### Internet Inspection Request from: Lynn Solmon corr made, ok to final