Inspections for the day of: Friday, June 15, 2007.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00028 FIR-Aging Inspection6/15/20076/15/20076/18/2007 10:04:48 AM DONE
Under construction, work in progress.
FIR07-00007 INSP-Final Inspection6/13/20076/15/20076/18/2007 9:52:18 AMPPASS
Fire alarm work passed final inspection.
MIS07-00135 FIR-Final6/14/20076/15/20076/18/2007 9:45:12 AMPFAIL
Provide current annual certification tags for the fire extinguishers, need to remove surface bolt at the back exit door.
FIR07-00448 INSP-Sprinkler Rough-in6/14/20076/15/20076/15/2007 2:28:03 PMPPART
UG fire supply line is approved for cover.
FIR06-00948 INSP-Final Inspection6/14/20076/15/20076/15/2007 2:27:05 PMANR
Outside bell does not function.
BLD06-00845 FIRE-Conference6/14/20076/15/20076/15/2007 11:50:53 AMADONE
On site visit to discuss status of fire alarm and sprinkler permitted work and issues for building life safety final.
BLD05-02144 FIRE-Final Inspection6/14/20076/15/20076/15/2007 10:37:46 AMAFAIL
Need to final project related hood suppression permit, fire sprinkler work is not complete, fire alarm needs reprogramming, post max. occupant load sign, attatch provided PFE's to the wall as discussed, need signage above the exit door with keyed locking hardware.
FIR05-00752 INSP-Final Inspection6/13/20076/15/20076/15/2007 10:33:39 AMAPART
Duct detectors need to initiate a supervisory signal, not alarm as currently programed, the remainder of tenant fire alarm work passed inspection, a shelf in the mech. room blocking strobe coverage removed while on site.
FIR05-00750 INSP-Final Inspection6/13/20076/15/20076/15/2007 10:28:20 AMAPART
TI fire alarm installation passed inspection, final pending shell and core fire alarm.
FIR06-01016 INSP-Sprinkler Rough-in6/14/20076/15/20076/15/2007 10:26:55 AMAPART
Items remaining to be completed include installation of dry pendents at the cooler and outside entryway, ceiling tile and escutcheons, other items on c/n are finished.
FIR06-00262 INSP-Final Inspection6/14/20076/15/20076/15/2007 9:04:45 AMAPASS
Fire supply line permit finaled.