ELE09-00900
| ELE-Aging Inspection | 6/15/2011 | 6/15/2011 | 6/15/2011 4:07:54 PM | | DONE |
|
|
still under construction, should be ready for final soon
|
ELE09-01570
| ELE-Aging Inspection | 6/15/2011 | 6/15/2011 | 6/15/2011 2:59:57 PM | | DONE |
|
|
still under construction, electrical contractor will call next week for final
|
ELE09-01198
| ELE-Aging Inspection | 6/15/2011 | 6/15/2011 | 6/15/2011 2:49:16 PM | | DONE |
|
|
still under construction
|
ELE11-01257
| Permanent Service | 6/15/2011 | 6/15/2011 | 6/15/2011 2:47:26 PM | P | PASS |
|
|
call Joe at ###-#### for access Phone #: ###-#### >> Inspection requested via web by PAT MILLER p/s u/g rec ok
|
ELE11-01261
| Final | 6/15/2011 | 6/15/2011 | 6/15/2011 2:20:56 PM | P | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov NEC 110.26(2) Working space in front of the electrical equipment shall be min. 30 in.
|
ELE11-01217
| Final | 6/15/2011 | 6/15/2011 | 6/15/2011 2:01:07 PM | P | FAIL |
|
|
CHANEY Phone #: ###-#### NEC320.12 A/C unit wired from disconnect to unit with AC cable. Not aceptable Must be wired in Liquidtight flex NEC.356
|
ELE11-00495
| Electrical Rough-In | 6/15/2011 | 6/15/2011 | 6/15/2011 1:25:21 PM | P | PASS |
|
|
clyde - radiant heat - 1412 unit - upstairs bathroom Phone #: ###-#### rough-in ok cover floor heat
|
ELE11-01086
| Electrical Rough-In | 6/14/2011 | 6/15/2011 | 6/15/2011 1:14:21 PM | P | PASS |
|
|
Toby Phone #: ###-#### >> Inspection requested via web by Sean DeLacy rough-in ok cover grid- seating area
|
ELE11-00999
| Electrical Rough-In | 6/15/2011 | 6/15/2011 | 6/15/2011 12:58:57 PM | P | PASS |
|
|
Ceiling cover, Pat Gill is contact, ###-#### thank you Phone #: ###-#### >> Inspection requested via web by Debby Ellis rough-in ok cover ceiling grid
|
ELE10-02515
| Final | 6/15/2011 | 6/15/2011 | 6/15/2011 12:35:27 PM | P | PASS |
|
|
gary Phone #: ###-#### final ok
|
GCE11-00060
| GCE-Temporary Service | 6/14/2011 | 6/15/2011 | 6/15/2011 10:18:47 AM | A | PASS |
|
|
Temp ServiceMark @ ###-#### or ###-####Call in advance t/s o/h ok
|
MIS11-00142
| ELE-Conference | 6/14/2011 | 6/15/2011 | 6/15/2011 10:01:45 AM | A | DONE |
|
|
Tawny or ###-#### Tracy--Please call at least 30 mins prior to inspection--also see scanned documents prior to inspection Phone #: ###-#### talk with renters dicussed there complants. Exposed wiring was mostly low voltage thermostat wiring. Dryer branch circuit in need of support (stapling) . Service panel at rear entrance requires an 2 in ko seal to plug hole.
|
ELE11-01222
| Electrical Rough-In | 6/14/2011 | 6/15/2011 | 6/15/2011 9:16:13 AM | A | PASS |
|
|
Please inspect re-wired floor between 1st and second floors for deck sheeting. Thank you! Phone #: ###-#### >> Inspection requested via web by Adam Staigle rough-in ok cover floor joist
|
ELE11-01246
| Final | 6/14/2011 | 6/15/2011 | 6/15/2011 8:58:00 AM | A | PASS |
|
|
lars Phone #: ###-#### final ok
|
ELE11-01254
| Temporary Service | 6/15/2011 | 6/15/2011 | 6/15/2011 8:32:03 AM | A | PASS |
|
|
THANKS Phone #: ###-#### >> Inspection requested via web by Bob Glenn t/s u/g ok
|
ELE11-00707
| Final | 6/14/2011 | 6/15/2011 | 6/14/2011 3:54:51 PM | A | PASS |
|
|
CODE 1968 Phone #: ###-#### >> Inspection requested via web by Bob Glenn final ok
|
ELE11-01036
| Electrical Rough-In | 6/14/2011 | 6/15/2011 | 6/14/2011 3:39:17 PM | A | PASS |
|
|
UNDERGROUND INSPECTION BRETT IS THERE WORKING PLEASE CALL MIKE AT ###-#### OR BRETT AT ###-#### IF YOU HAVE ANY QUESTIONS. Phone #: ###-#### >> Inspection requested via web by Mike TenHulzen rough-in ok cover trench
|
ELE11-01222
| Electrical Rough-In | 6/10/2011 | 6/15/2011 | 6/13/2011 8:03:02 AM | A | NR |
|
|
Please inspect re-wired floor between 1st and second floors for deck sheeting. Thank you! Phone #: ###-#### >> Inspection requested via web by Adam Staigle
|