FIR12-00189
| INSP-Sprinkler Rough-in/Hydro | 6/14/2012 | 6/15/2012 | 6/15/2012 4:09:03 PM | P | NR |
|
|
Charles Phone #: ###-#### *rescheduled per contractor request
|
FIR12-00246
| INSP-Sprinkler Rough-in | 6/15/2012 | 6/15/2012 | 6/15/2012 4:08:04 PM | P | PART |
|
|
East wing dry and wet system rough-in inspection as annotated and dated on stamped plans okayed. One seismic brace at the 3" dry main needs relocated per plan.
|
FIR12-00301
| INSP-Sprinkler Rough-in | 6/15/2012 | 6/15/2012 | 6/15/2012 4:04:59 PM | P | PART |
|
|
Overhead fire sprinkler system modifications are approved for cover at the remodel area.
|
FIR12-00066
| INSP-Final Inspection | 6/13/2012 | 6/15/2012 | 6/15/2012 1:37:59 PM | A | NR |
|
|
Steve Phone #: ###-####
|
FIR12-00068
| INSP-Final Inspection | 6/13/2012 | 6/15/2012 | 6/15/2012 1:15:32 PM | A | FAIL |
|
|
Signals not recieved by offsite monitoring.
|
FIR12-00088
| INSP-Final Inspection | 6/13/2012 | 6/15/2012 | 6/15/2012 1:12:12 PM | A | FAIL |
|
|
Communication failure needs repaired.
|
FIR12-00064
| INSP-Final Inspection | 6/13/2012 | 6/15/2012 | 6/15/2012 1:01:58 PM | A | NR |
|
|
Communication fault needs repaired prior to final.
|
BLD12-00217
| FIRE-Final Inspection | 6/14/2012 | 6/15/2012 | 6/15/2012 12:52:00 PM | A | PASS |
|
|
Fire life safety inspection passed.
|
FIR12-00154
| INSP-Final Inspection | 6/14/2012 | 6/15/2012 | 6/15/2012 12:50:59 PM | A | PASS |
|
|
Fire alarm work passed inspection. Note- in duct detector deleted due to relocated HVAC ducting (fire damper no longer required).
|
FIR12-00162
| INSP-Final Inspection | 6/14/2012 | 6/15/2012 | 6/15/2012 12:46:18 PM | A | PASS |
|
|
Scope of work completed. Fire sprinkler permit finaled.
|
FIR12-00020
| INSP-Sprinkler Rough-in/Hydro | 6/14/2012 | 6/15/2012 | 6/15/2012 12:42:41 PM | A | PART |
|
|
UG fire supply line hydrostatic test completed satisfactory.
|
BLD11-01532
| FIRE-Final Inspection | 6/14/2012 | 6/15/2012 | 6/15/2012 12:36:50 PM | A | FAIL |
|
|
Post one fire extinguisher at the second level office area, need access for inspection at unit 133, discussed fire code review note items and project attatched fire alarm permit (voided status).
|