Inspections for the day of: Friday, June 15, 2012.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00189 INSP-Sprinkler Rough-in/Hydro6/14/20126/15/20126/15/2012 4:09:03 PMPNR
Charles Phone #: ###-#### *rescheduled per contractor request
FIR12-00246 INSP-Sprinkler Rough-in6/15/20126/15/20126/15/2012 4:08:04 PMPPART
East wing dry and wet system rough-in inspection as annotated and dated on stamped plans okayed. One seismic brace at the 3" dry main needs relocated per plan.
FIR12-00301 INSP-Sprinkler Rough-in6/15/20126/15/20126/15/2012 4:04:59 PMPPART
Overhead fire sprinkler system modifications are approved for cover at the remodel area.
FIR12-00066 INSP-Final Inspection6/13/20126/15/20126/15/2012 1:37:59 PMANR
Steve Phone #: ###-####
FIR12-00068 INSP-Final Inspection6/13/20126/15/20126/15/2012 1:15:32 PMAFAIL
Signals not recieved by offsite monitoring.
FIR12-00088 INSP-Final Inspection6/13/20126/15/20126/15/2012 1:12:12 PMAFAIL
Communication failure needs repaired.
FIR12-00064 INSP-Final Inspection6/13/20126/15/20126/15/2012 1:01:58 PMANR
Communication fault needs repaired prior to final.
BLD12-00217 FIRE-Final Inspection6/14/20126/15/20126/15/2012 12:52:00 PMAPASS
Fire life safety inspection passed.
FIR12-00154 INSP-Final Inspection6/14/20126/15/20126/15/2012 12:50:59 PMAPASS
Fire alarm work passed inspection. Note- in duct detector deleted due to relocated HVAC ducting (fire damper no longer required).
FIR12-00162 INSP-Final Inspection6/14/20126/15/20126/15/2012 12:46:18 PMAPASS
Scope of work completed. Fire sprinkler permit finaled.
FIR12-00020 INSP-Sprinkler Rough-in/Hydro6/14/20126/15/20126/15/2012 12:42:41 PMAPART
UG fire supply line hydrostatic test completed satisfactory.
BLD11-01532 FIRE-Final Inspection6/14/20126/15/20126/15/2012 12:36:50 PMAFAIL
Post one fire extinguisher at the second level office area, need access for inspection at unit 133, discussed fire code review note items and project attatched fire alarm permit (voided status).