FIR16-00212
| INSP-Sprinkler Rough-in | 6/15/2016 | 6/15/2016 | 6/15/2016 2:28:26 PM | P | CANC |
|
|
Inspection request scheduled for wrong day, inspection rescheduled for 16June16
|
FIR16-00358
| INSP-Final Inspection | 6/14/2016 | 6/15/2016 | 6/15/2016 12:00:58 PM | A | PASS |
|
|
Final fire sprinkler inspection passed/complete
|
BLD16-01967
| FIRE-Final Inspection | 6/14/2016 | 6/15/2016 | 6/15/2016 10:58:26 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguishers are in place with current inspection tags, door hardware is existing (round type door hardware), no door hardware upgrading. Final life fire safety inspection passed/complete.
|
FIR15-00831
| INSP-Sprinkler Rough-in | 6/15/2016 | 6/15/2016 | 6/15/2016 10:42:10 AM | P | PASS |
|
|
Rough to cover inspection for fire sprinkler piping above gridded area's on level 6 complete, fire sprinkler above gridded area's approved for cover.
|
FIR15-00861
| INSP-Sprinkler Rough-in | 6/15/2016 | 6/15/2016 | 6/15/2016 10:41:23 AM | P | PASS |
|
|
Rough to cover inspection for fire sprinkler piping above gridded area's on level 7 complete, fire sprinkler above gridded area's approved for cover.
|
FIR15-00767
| INSP-Final Inspection | 6/14/2016 | 6/15/2016 | 6/15/2016 10:08:04 AM | A | PART |
|
|
Tested smokes and A/V's on level 7, level 6, level 5 and level 4, all devices tested properly. Tested elevator recall as well as elevator shunt trip, devices tested corectly. Tested HVAC unit shutdown for in-duct smoke detectors on level 2, all tested correctly. Items left to inspect, associated devices with fire sprinkler system and VESDA systems.
|
FIR16-00070
| INSP-Final Inspection | 6/14/2016 | 6/15/2016 | 6/14/2016 2:33:54 PM | A | CANC |
|
|