Inspections for the day of: Friday, June 15, 2018.
Number of inspections: 20
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00443 INSP-Final Inspection6/15/20186/15/20186/15/2018 4:49:29 PMPPASS
Final fire alarm inspection for area of work complete.

Zack-call 30 mins ahead Phone #: ###-####
FIR18-00474 INSP-Final Inspection6/15/20186/15/20186/15/2018 4:49:16 PMPPASS
Final fire alarm inspection for area of work complete.

Zack-call 30 mins ahead Phone #: ###-####
FIR18-00124 INSP-Final Inspection6/15/20186/15/20186/15/2018 3:30:50 PMPPART
Partial final inspection for fire alarm system complete, hood suppression system interface with fire alarm complete, fire sprinkler interface with alarm complete, audio visual notification complete, monitoring and signal verfication complete, ony item left to inspect is elevator recall and shunt when elevator is complete. TCO for fire alarms authorized for employee training only.
BLD18-01995 FIRE-Final Inspection6/14/20186/15/20186/15/2018 3:08:58 PMPFAIL
The property address has an outstanding FIR permit that has never been finaled (FIR14-00127) FIR per mit for this fire alarm work needs to be finaled before this life fire safety inspection can be completed.

Richard Phone #: ###-####
BLD18-00266 FIRE-Final Inspection6/15/20186/15/20186/15/2018 3:00:08 PMPFAIL
Called point of contact for inspection request, left a message with a return phone number, went to tenant space and personnel inside didi not know who Amanda was, inspection request will need to be rescheduled.

Amanda Phone #: ###-####
FIR18-00309 INSP-Final Inspection6/14/20186/15/20186/15/2018 2:29:30 PMPPASS
Previously noted items have been completed, final fire alarm inspection for area of work complete.

Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa
BLD17-01763 FIRE-Final Inspection6/14/20186/15/20186/15/2018 12:54:22 PMAPART
Partial life fire safety inspection is complete, fire sprinkler inspection is complete, fire alarm inspection is partially complete (see fire alarm comments under FIR18-00124), fire extinguishers are in place with current inspection tags, knox boxes are located by the main east entrance and another on the west side of the building.



Items that need to be corrected before final C of O, install emergency egress lighting and interior emergency lighting as discussed and marked on city approved drawings, rotate fire hydrant to correct orientation, provide documentation for testing of refrigerant detection system and alarm.


TCO for life fire safety authorized per conversation with Adele for EMPLOYEE TRAINING ONLY, all fire sprinkler systems and fire alarm system to remain active after this inspection.
FIR17-00627 INSP-Final Inspection6/15/20186/15/20186/15/2018 12:42:03 PMPPASS
Final underground supply inspection complete.
FIR17-00689 INSP-Final Inspection6/15/20186/15/20186/15/2018 12:41:32 PMPPASS
Final fire sprinkler inspection complete.
FIR18-00473 INSP-Final Inspection6/14/20186/15/20186/15/2018 12:37:46 PMAPASS
Final commercial hood fire suppression inspection complete.

Dave Phone #: ###-####
FIR18-00472 INSP-Final Inspection6/14/20186/15/20186/15/2018 12:37:24 PMAPASS
Final commercial hood fire suppression inspection complete.

Dave Phone #: ###-####
FIR18-00471 INSP-Final Inspection6/14/20186/15/20186/15/2018 12:37:05 PMAPASS
Final commercial hood fire suppression inspection complete.

Dave Phone #: ###-####
FIR18-00470 INSP-Final Inspection6/14/20186/15/20186/15/2018 12:36:50 PMAPASS
Final commercial hood fire suppression inspection complete.

Dave Phone #: ###-####
FIR18-00468 INSP-Final Inspection6/14/20186/15/20186/15/2018 12:36:27 PMAPASS
Final commercial hood fire suppression inspection complete.

Dave Phone #: ###-####
FIR18-00467 INSP-Final Inspection6/14/20186/15/20186/15/2018 12:36:08 PMAPASS
Final commercial hood fire suppression inspection complete.

Dave Phone #: ###-####
FIR18-00466 INSP-Final Inspection6/14/20186/15/20186/15/2018 12:35:52 PMAPASS
Final commercial hood fire suppression inspection complete.

Dave Phone #: ###-####
FIR18-00469 INSP-Final Inspection6/14/20186/15/20186/15/2018 12:35:14 PMAFAIL
Gas valve did not shut when suppression system was activate, after repairs are made a re-inspection will be required.

Dave Phone #: ###-####
BLD17-04457 FIRE-Final Inspection6/14/20186/15/20186/15/2018 8:21:50 AMAPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection complete.

Tim Phone #: ###-####
BLD17-02765 FIRE-Final Inspection6/14/20186/15/20186/15/2018 8:21:31 AMAPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection complete.

Tim Phone #: ###-####
FIR18-00043 INSP-Final Inspection6/14/20186/15/20186/15/2018 8:19:28 AMAPASS
Previously noted items have been repaired, final fire alarm inspection complete.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price