Inspections for the day of: Monday, June 15, 2020.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC20-01221 Final6/12/20206/15/20206/15/2020 3:40:06 PMPFAIL
garage code 0425 or 3484 or 1225 Phone #: ###-#### Inspection requested via web by Oleg Chervak- condenser installed does not match approved man j shows carrier has payne installed- replace with right equipment and reschedule
MEC20-02285 Final6/8/20206/15/20206/15/2020 2:49:05 PMPPASS
INSTALLER GERRY ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace a/c coil co locking caps ok-
MEC20-02334 Final6/11/20206/15/20206/15/2020 2:20:24 PMPFAIL
Please call David prior to arrival at ###-#### Phone #: ###-#### Inspection requested via web by Andrea Grigsby- electric furnace coil heat pump ok- need 1 more locking cap installed on suction line- need co detector installed near bedroom- send pic for reinspect of both corrections
MEC20-02280 Final6/8/20206/15/20206/15/2020 1:32:06 PMPPASS
INSTALLER DUSTIN ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace a/c coil co locking caps ok
MEC20-02194 Final6/11/20206/15/20206/15/2020 1:19:51 PMPNH
Please call Elizabeth prior to arrival at ###-#### Phone #: ###-#### Inspection requested via web by Andrea Grigsby- called twice no answer- texted once no reply- went by no one home- left notice- reschedule
MEC20-02246 Final6/15/20206/15/20206/15/2020 12:56:26 PMPPASS
final ok- no mantel will be installed
MEC20-02246 Rough-in6/15/20206/15/20206/15/2020 12:55:35 PMPPASS
call ###-#### when on the way Phone #: ###-#### Inspection requested via web by Lindsey Stegemann- fireplace R/I ok
MEC20-02137 Rough-in6/15/20206/15/20206/15/2020 12:49:15 PMPPASS
Phone #: ###-#### Inspection requested via web by Kelton Tackett- R/I ok- insulation ok- need 10mil inert tape exterior penetration at meter location by final
MEC20-02137 Pressure Test6/15/20206/15/20206/15/2020 12:44:09 PMPPASS
Phone #: ###-#### Inspection requested via web by Kelton Tackett- 20lb gas pass tagged meter location
MEC20-02101 Rough-in6/12/20206/15/20206/15/2020 11:10:03 AMAFAIL
Phone #: ###-#### Inspection requested via web by Terek Worley
1- need city approved man j onsite
2- 6" fresh air can not tie into R/A can needs tied in near furnace
3- R/A ducting ran between trusses needs insulated to minimum R-6
4- need to fix all rips and tears in arma flex in crawl and near furnace

notice posted front window
MEC20-02101 Pressure Test6/12/20206/15/20206/15/2020 11:04:12 AMAPASS
Phone #: ###-#### Inspection requested via web by Terek Worley- 20lb gas pass tagged meter location
MEC20-02389 Rough-in6/12/20206/15/20206/15/2020 9:59:52 AMAPASS
Rough in to start insulating round duct. Francisco is the contact Phone #: ###-#### Inspection requested via web by stan lillquist-approved prints onsite- zone 2 seal on duct ok- ok to insulate- need lineset ran still- call in R/I when ready for cover
MEC20-02246 Rough-in6/12/20206/15/20206/15/2020 9:29:57 AMAFAIL
Call ###-#### when on the way Phone #: ###-#### Inspection requested via web by Lindsey Stegemann- metal draftstop behind fireplace does not cover wood framing has gap- recall in when fixed
MEC20-02153 Pressure Test6/12/20206/15/20206/15/2020 8:55:09 AMAFAIL
please call Rick at ###-#### and give him 1 hour head notice. Phone #: ###-#### Inspection requested via web by Mary Jane Schmidt- need to add range hood to permit and call in for inspection on range hood- gas piping at meter needs open tee installed between 2 shut off valves or section test- retest gas line
MEC19-05108 Mec-Aging Inspection6/15/20206/15/20206/15/2020 8:02:50 AM FAIL
contractor needs to schedule final inspection- permit will expire next aging if no activity
MEC20-02192 Final6/15/20206/15/20206/15/2020 7:57:48 AMAPASS
corrections made