MEC20-01221
| Final | 6/12/2020 | 6/15/2020 | 6/15/2020 3:40:06 PM | P | FAIL |
|
|
garage code 0425 or 3484 or 1225 Phone #: ###-#### Inspection requested via web by Oleg Chervak- condenser installed does not match approved man j shows carrier has payne installed- replace with right equipment and reschedule
|
MEC20-02285
| Final | 6/8/2020 | 6/15/2020 | 6/15/2020 2:49:05 PM | P | PASS |
|
|
INSTALLER GERRY ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace a/c coil co locking caps ok-
|
MEC20-02334
| Final | 6/11/2020 | 6/15/2020 | 6/15/2020 2:20:24 PM | P | FAIL |
|
|
Please call David prior to arrival at ###-#### Phone #: ###-#### Inspection requested via web by Andrea Grigsby- electric furnace coil heat pump ok- need 1 more locking cap installed on suction line- need co detector installed near bedroom- send pic for reinspect of both corrections
|
MEC20-02280
| Final | 6/8/2020 | 6/15/2020 | 6/15/2020 1:32:06 PM | P | PASS |
|
|
INSTALLER DUSTIN ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace a/c coil co locking caps ok
|
MEC20-02194
| Final | 6/11/2020 | 6/15/2020 | 6/15/2020 1:19:51 PM | P | NH |
|
|
Please call Elizabeth prior to arrival at ###-#### Phone #: ###-#### Inspection requested via web by Andrea Grigsby- called twice no answer- texted once no reply- went by no one home- left notice- reschedule
|
MEC20-02246
| Final | 6/15/2020 | 6/15/2020 | 6/15/2020 12:56:26 PM | P | PASS |
|
|
final ok- no mantel will be installed
|
MEC20-02246
| Rough-in | 6/15/2020 | 6/15/2020 | 6/15/2020 12:55:35 PM | P | PASS |
|
|
call ###-#### when on the way Phone #: ###-#### Inspection requested via web by Lindsey Stegemann- fireplace R/I ok
|
MEC20-02137
| Rough-in | 6/15/2020 | 6/15/2020 | 6/15/2020 12:49:15 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kelton Tackett- R/I ok- insulation ok- need 10mil inert tape exterior penetration at meter location by final
|
MEC20-02137
| Pressure Test | 6/15/2020 | 6/15/2020 | 6/15/2020 12:44:09 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kelton Tackett- 20lb gas pass tagged meter location
|
MEC20-02101
| Rough-in | 6/12/2020 | 6/15/2020 | 6/15/2020 11:10:03 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Terek Worley 1- need city approved man j onsite 2- 6" fresh air can not tie into R/A can needs tied in near furnace 3- R/A ducting ran between trusses needs insulated to minimum R-6 4- need to fix all rips and tears in arma flex in crawl and near furnace
notice posted front window
|
MEC20-02101
| Pressure Test | 6/12/2020 | 6/15/2020 | 6/15/2020 11:04:12 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Terek Worley- 20lb gas pass tagged meter location
|
MEC20-02389
| Rough-in | 6/12/2020 | 6/15/2020 | 6/15/2020 9:59:52 AM | A | PASS |
|
|
Rough in to start insulating round duct. Francisco is the contact Phone #: ###-#### Inspection requested via web by stan lillquist-approved prints onsite- zone 2 seal on duct ok- ok to insulate- need lineset ran still- call in R/I when ready for cover
|
MEC20-02246
| Rough-in | 6/12/2020 | 6/15/2020 | 6/15/2020 9:29:57 AM | A | FAIL |
|
|
Call ###-#### when on the way Phone #: ###-#### Inspection requested via web by Lindsey Stegemann- metal draftstop behind fireplace does not cover wood framing has gap- recall in when fixed
|
MEC20-02153
| Pressure Test | 6/12/2020 | 6/15/2020 | 6/15/2020 8:55:09 AM | A | FAIL |
|
|
please call Rick at ###-#### and give him 1 hour head notice. Phone #: ###-#### Inspection requested via web by Mary Jane Schmidt- need to add range hood to permit and call in for inspection on range hood- gas piping at meter needs open tee installed between 2 shut off valves or section test- retest gas line
|
MEC19-05108
| Mec-Aging Inspection | 6/15/2020 | 6/15/2020 | 6/15/2020 8:02:50 AM | | FAIL |
|
|
contractor needs to schedule final inspection- permit will expire next aging if no activity
|
MEC20-02192
| Final | 6/15/2020 | 6/15/2020 | 6/15/2020 7:57:48 AM | A | PASS |
|
|
corrections made
|