FIR03-00175
| INSP-Supply line flush | 6/13/2003 | 6/16/2003 | 6/16/2003 12:00:00 AM | A | FAIL |
|
|
United water did not have the underground water supply turned on so we couldn't do the test 6/16/2003 11:02:36 AM
|
FIR03-00175
| INSP-Sprinkler Rough-in/Hydro | 6/13/2003 | 6/16/2003 | 6/16/2003 12:00:00 AM | A | FAIL |
|
|
all previous items on the correction notice have not been corrected 6/16/2003 11:04:16 AM
|
FIR03-00289
| INSP-Supply line flush | 6/13/2003 | 6/16/2003 | 6/16/2003 12:00:00 AM | A | PART |
|
|
The inspection was for the cover of the underground supply piping. The piping is ok to cover 6/17/2003 9:47:03 AM
|
FIR02-00500
| INSP-Final Inspection | 6/13/2003 | 6/16/2003 | 6/16/2003 12:00:00 AM | A | FAIL |
|
|
The map provided does not show exact initiating device location or address. Provide correct address 6/16/2003 11:35:08 AM
|
FIR02-00500
| INSP-Final Inspection | 6/16/2003 | 6/16/2003 | 6/16/2003 12:00:00 AM | A | PASS |
|
|
Map and signs provied
|
FIR03-00193
| INSP-Final Inspection | 6/12/2003 | 6/16/2003 | 6/16/2003 12:00:00 AM | P | FAIL |
|
|
relocate smoke detector to with in 5' of the door and test. Provie map at facp. Provide sign on door. Test the duct smoke detector and test current draw of the panel for battery size verification 6/16/2003 3:10:38 PM
|
BLD03-00300
| FIRE-Final Inspection | 6/16/2003 | 6/16/2003 | 6/16/2003 12:00:00 AM | P | PASS |
|
|
OK for perm occupancy 6/16/2003 4:06:46 PM
|
FIR03-00214
| INSP-Sprinkler Rough-in/Hydro | 6/16/2003 | 6/16/2003 | 6/16/2003 12:00:00 AM | P | PASS |
|
|
bruce; Phone #: ###-#### Underground supply line hydro test is OK 6/16/2003 1:47:56 PM
|