Inspections for the day of: Wednesday, June 16, 2004.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00612 INSP-Final Inspection6/15/20046/16/20046/16/2004 12:00:00 AMAFAIL
Provide verification of signals, provide map at the facp, repair the fire/smoke dampers as listed on the plans and swap a/v's in room 109. Structural inspector said they would verify operation of the single station smoke detectors. This inspection lasted 5 1/2 hours. I was unable to perform the life safety and fire sprinkler inspections. 6/16/2004 3:34:18 PM
FIR04-00329 INSP-Final Inspection6/15/20046/16/20046/16/2004 12:00:00 AMAPASS
Fire sprinkler finaled. Dry pipe valve operated correctly and alarm points arrived at the facp 6/16/2004 3:28:28 PM
FIR04-00307 INSP-Final Inspection6/15/20046/16/20046/16/2004 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 6/15/2004 at 9:13:30 AM. Contact: ###-####.
FIR03-00448 INSP-Final Inspection6/16/20046/16/20046/16/2004 12:00:00 AMPFAIL
Per the sprinkler fitter, he could not get the forward flush to pass. He will need to repipe drains. Room 203 sprinkler canopy is missing. Could not perform complete sprinkler inspection due to fire alarm inspection taking so long. 6/16/2004 3:42:43 PM