FIR03-00612
| INSP-Final Inspection | 6/15/2004 | 6/16/2004 | 6/16/2004 12:00:00 AM | A | FAIL |
|
|
Provide verification of signals, provide map at the facp, repair the fire/smoke dampers as listed on the plans and swap a/v's in room 109. Structural inspector said they would verify operation of the single station smoke detectors. This inspection lasted 5 1/2 hours. I was unable to perform the life safety and fire sprinkler inspections. 6/16/2004 3:34:18 PM
|
FIR04-00329
| INSP-Final Inspection | 6/15/2004 | 6/16/2004 | 6/16/2004 12:00:00 AM | A | PASS |
|
|
Fire sprinkler finaled. Dry pipe valve operated correctly and alarm points arrived at the facp 6/16/2004 3:28:28 PM
|
FIR04-00307
| INSP-Final Inspection | 6/15/2004 | 6/16/2004 | 6/16/2004 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 6/15/2004 at 9:13:30 AM. Contact: ###-####.
|
FIR03-00448
| INSP-Final Inspection | 6/16/2004 | 6/16/2004 | 6/16/2004 12:00:00 AM | P | FAIL |
|
|
Per the sprinkler fitter, he could not get the forward flush to pass. He will need to repipe drains. Room 203 sprinkler canopy is missing. Could not perform complete sprinkler inspection due to fire alarm inspection taking so long. 6/16/2004 3:42:43 PM
|