Inspections for the day of: Thursday, June 16, 2005.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-01298 BLD-Aging Inspection6/16/20056/16/20056/20/2005 3:12:26 PMPDONE
Spoke with Russ at ###-####, who refered me to Jerry Weaver at ###-#### whom I contacted and left a message in regards to the aging permit and the need for a final inspection and sign off.
FIR05-00265 INSP-Sprinkler Rough-in6/16/20056/16/20056/16/2005 4:33:50 PMPFAIL
Underground piping must meet min. depth of bury req. NFPA 10.4.1, backfill at rock per 10.9.4, support per 10.7.9, distance from embankment per 10.5.4, and meet deflection requirements. The pipe laid over the large section of embeded rock in the trench fails to meet code standards and requirements.
FIR05-00272 INSP-Supply line flush6/15/20056/16/20056/16/2005 4:17:11 PMPFAIL
Installation does not match approved plans, pipe routing has been changed significantly.
BLD04-00313 FIRE-Final Inspection6/15/20056/16/20056/16/2005 2:09:39 PMPFAIL
Provide current inspection tag on installed fire ext., provide sinage above main entry/ exit door.
FIR05-00282 INSP-Sprinkler Rough-in/Hydro6/16/20056/16/20056/16/2005 1:22:42 PMPCANC
Wrong permit number called in. This inspection was for UG hydro and flush under permit fir05-00206 at the same address under the same building permit.
FIR05-00045 INSP-Supply line flush6/14/20056/16/20056/16/2005 12:22:46 PMAPART
Underground fire supply line hydro and flush both passed inspection.
FIR05-00344 INSP-Sprinkler Rough-in/Hydro6/16/20056/16/20056/16/2005 12:01:58 PMPPART
Beam clamps and retaining straps on hangers in theaters verified, two hangers missing straps and one hanger with strap not attatched to beam....these hangers were corrected while on site.
FIR05-00160 INSP-Final Inspection6/16/20056/16/20056/16/2005 11:23:24 AMPPASS
Fire sprinkler finaled, Troy Cobbley has tested the flow switch during alarm testing under the associated fire alarm permit fir05-00232.
BLD04-00094 FIRE-Final Inspection6/14/20056/16/20056/16/2005 10:35:27 AMAPART
Life safety issues passed inspection, final pending sign off on sprinkler permit fir05-00160 (flow switch test).
BLD05-01107 FIRE-Conference6/15/20056/16/20056/16/2005 8:27:57 AMADONE
Discussed emergency lighting placement and exit sign locations with Tim the GC and electrical contractor.
BLD04-00094 FIRE-Final Inspection6/16/20056/16/20056/16/2005 12:00:00 AMPPASS
Fire life safety finaled.
FIR05-00206 INSP-Sprinkler Rough-in/Hydro6/16/20056/16/20056/16/2005 12:00:00 AMPPASS
Underground fire supply line hydrostatic test and flush passed inspection.
MIS04-00258 BLD-Final6/16/20056/16/20056/16/2005 12:00:00 AMPPASS
Fire life safety finaled.