ELE06-02013
| Final | 6/16/2006 | 6/16/2006 | 6/16/2006 3:53:38 PM | P | PASS |
|
|
dennis; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok card signed
|
ELE06-02228
| Permanent Service | 6/16/2006 | 6/16/2006 | 6/16/2006 3:20:18 PM | P | FAIL |
|
|
Please call my cell if you have any questions. Thanks, Randy; Phone #: ###-#### Internet Inspection Request from: Randy Fletcher called needs #4 GEC to water, no violations retained address both subpanels , range dryer feeds, remove sprinkler and flex fittings from emt, label panels, seal KOs job not ready
|
ELE06-02207
| Rough-In Permanent Service | 6/16/2006 | 6/16/2006 | 6/16/2006 2:44:28 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. not made fee due, called 300.4(A)(1)&(D) nail plates and 11/4" from inside and outside edges
|
ELE06-02226
| Electrical Rough-In | 6/16/2006 | 6/16/2006 | 6/16/2006 2:01:02 PM | P | NH |
|
|
oga; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles notice posted called
|
ELE06-00935
| Final | 6/16/2006 | 6/16/2006 | 6/16/2006 1:21:25 PM | P | NR |
|
|
kyle ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley talked with electricians on site not ready
|
ELE06-02142
| Rough-In Permanent Service | 6/16/2006 | 6/16/2006 | 6/16/2006 1:05:50 PM | P | PASS |
|
|
###-####. r/i p/s u/g new ok
|
ELE06-02131
| Electrical Rough-In | 6/13/2006 | 6/16/2006 | 6/16/2006 12:25:14 PM | P | PART |
|
|
r/i u/g uf and concrete cover for electrode ok only
|
ELE06-02131
| Permanent Service | 6/16/2006 | 6/16/2006 | 6/16/2006 12:24:00 PM | P | PASS |
|
|
Service change 200 amp to 400 amp. Id Power disconnecting at 9:00 am. Inspection required for reconnect.; Phone #: ###-#### Internet Inspection Request from: Julie Schroder p/s u/g rec. ok
|
ELE05-04666
| Final | 6/16/2006 | 6/16/2006 | 6/16/2006 11:55:51 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 6/16/2006 at 8:22:10 AM. Contact: ###-####. final ok UL ok for x-ray unit
|
ELE06-01542
| Electrical Rough-In | 6/15/2006 | 6/16/2006 | 6/16/2006 10:56:14 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 6/15/2006 at 4:19:01 PM. Contact: ###-####. r/i walls and ceilings ok new rest rms also bond water system(new) to building p/s
|
ELE06-02227
| Final | 6/15/2006 | 6/16/2006 | 6/16/2006 10:19:32 AM | A | FAIL |
|
|
may enter through gate on east side of house. Curtis; Phone #: ###-#### Internet Inspection Request from: Curtis Dunham corr. called needs outlet for spa, bonding for spa, calc p/s for size, spa not listed, use manufactures breakers only
|
ELE06-01488
| Final | 6/15/2006 | 6/16/2006 | 6/16/2006 9:42:20 AM | A | FAIL |
|
|
Work performed by Joe Schneehagen; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz 314.20 needs box extensions kit & micro wave outlets, 210.52 outlet above baseboard heater, 410.8 (BCD) needs approved fixture closet, 406.3 grded outlets on non grd circuit replace, gfic protect and labels you choose corr. called
|
ELE06-01807
| Electrical Rough-In | 6/16/2006 | 6/16/2006 | 6/16/2006 8:51:05 AM | A | FAIL |
|
|
A.M. rough-in inspection for the ceiling in the customer areas. Thanks.; Phone #: ###-#### Internet Inspection Request from: Steve Syltie corr. not made
|
ELE06-02219
| Temporary Service | 6/15/2006 | 6/16/2006 | 6/16/2006 8:03:36 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 6/15/2006 at 2:54:11 PM. Contact: ###-####. t/s u/g new ok
|