Inspections for the day of: Friday, June 16, 2006.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-00319 ELE-Aging Inspection6/16/20066/16/20066/16/2006 4:18:01 PM DONE
project is suc.
ELE06-02210 Temporary Service6/16/20066/16/20066/16/2006 4:04:49 PMPPASS
joe - reinsp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr made, t/s u/g n ok
ELE06-02209 Temporary Service6/16/20066/16/20066/16/2006 4:02:05 PMPPASS
joe - reinsp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr made, t/s u/g n ok
ELE06-00457 Final6/16/20066/16/20066/16/2006 3:48:49 PMPPART
rock; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called contr to say core and shell must be finalled before t/l. Told contr labels required for panels, rest ok
ELE06-00784 Final6/16/20066/16/20066/16/2006 3:07:43 PMPPASS
paul; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ok to final
ELE06-02236 Electrical Rough-In6/16/20066/16/20066/16/2006 2:15:42 PMPPASS
Scheduled by a contractor via Hello! on 6/16/2006 at 11:28:08 AM. Contact: ###-####. ok to cover u/g
ELE06-02229 Rough-In Permanent Service6/16/20066/16/20066/16/2006 1:46:28 PMPFAIL
verna; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called, left corr notice, nec 300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing members,BCC all make-up shall be done, boxes installed
ELE06-02208 Electrical Rough-In6/16/20066/16/20066/16/2006 1:15:32 PMPPASS
joe - reinsp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr made, ric ok, p/s u/g n ok
ELE06-01922 Electrical Rough-In6/15/20066/16/20066/16/2006 12:07:15 PMAPASS
Equal potential plane for hot tub; Phone #: ###-#### Internet Inspection Request from: Jari Rivers ok to pour for hot tub
ELE06-02216 Rough-In Permanent Service6/15/20066/16/20066/16/2006 11:55:27 AMAPASS
lynn ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ric ok, p/s u/g n ok
ELE06-00113 Electrical Rough-In6/15/20066/16/20066/16/2006 10:25:44 AMAPART
contact: Greg Pack - 5th floor inspection; Phone #: ###-#### Internet Inspection Request from: Deb McCoy 5th walls, 5-11 #1 stairwells anop ok to cover
ELE06-02142 Rough-In Permanent Service6/16/20066/16/20066/16/2006 10:03:12 AMANR
Scheduled by a contractor via Hello! on 6/16/2006 at 6:56:45 AM. Contact: ###-####. will call for ltr
ELE06-01464 Final6/15/20066/16/20066/16/2006 9:21:56 AMAPASS
Scheduled by a contractor via Hello! on 6/15/2006 at 4:19:45 PM. Contact: ###-####. corr made, ok to final
ELE06-02225 Rough-In Permanent Service6/15/20066/16/20066/16/2006 8:56:32 AMAFAIL
dino; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called, left corr notice,nec 250.64(C)&(D) gec shall be continuous or tapped outside enclosure, 300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing member, 334.23 nm cable shall comply with 320.23 in attic space, BCC all make-up shall be done,boxes installed,approved set of plans on job. Note: 38 rooms