Inspections for the day of: Friday, June 16, 2006.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00321 INSP-Sprinkler Rough-in/Hydro6/16/20066/16/20066/19/2006 8:54:18 AMPDEFR
To be rescheduled due to time constraints.
FIR06-00368 INSP-Final Inspection6/15/20066/16/20066/19/2006 8:53:29 AMACANC
No time available to complete this inspection today, to be rescheduled.
BLD05-03270 FIRE-Final Inspection6/15/20066/16/20066/16/2006 3:13:10 PMAPASS
Fire life safety inspection is satisfactory, provided fire extinguishers mounted on the wall as discussed while on site.
FIR06-00415 INSP-Final Inspection6/15/20066/16/20066/16/2006 3:10:40 PMAPASS
The hood suppression system operated correctly under test conditions.
BLD05-02148 FIRE-Final Inspection6/15/20066/16/20066/16/2006 2:22:40 PMAFAIL
Not all required provisions for life safety final have been met at this stage of building completion, need adequate FD access around new addition, three exit signs above old exits from the existing south wall to be covered if exits are no longer to be used, exit door hardware, exit signs, emergency lights an PFE's in the new addition are acceptable for those portions installed, the racking in the new addition is not to be utilized until permitted and approved.
FIR05-00819 INSP-Final Inspection6/15/20066/16/20066/16/2006 2:12:59 PMAPASS
Required corrections have been made and verified for completion, final inspection for the permitted work passed.
FIR06-00428 INSP-Final Inspection6/15/20066/16/20066/16/2006 2:06:54 PMAPASS
Fire alarm work is acceptable, inspection passed.
FIR04-00753 INSP-Supply line flush6/15/20066/16/20066/16/2006 2:05:49 PMAPART
Fire supply line flush performed satisfactory.
FIR05-00772 INSP-Sprinkler Rough-in6/15/20066/16/20066/16/2006 12:06:25 PMAPART
UG fire supply line riser and stub-out appears satisfactory, no approved plans on site for verification of pipe size, etc., need to provide means for seismic clearance where the ductile riser will pass through floor slab, need to cover open ended MJ x flange adaptor at riser piece.
FIR06-00293 INSP-Sprinkler Rough-in/Hydro6/15/20066/16/20066/16/2006 11:34:23 AMAPART
Heads at the drop ceiling areas as marked on approved plans are okay to cover, armovers at two locations have overspaced hangers, area to the south and one room at the west not completed for inspection at this time.
FIR06-00314 INSP-Final Inspection6/15/20066/16/20066/16/2006 10:35:49 AMAPASS
Fire sprinkler work is acceptable, one HVAC register to be relocated a min. 1' away from a pendent at the west side-to be verified at life safety final.
BLD06-01524 FIRE-Final Inspection6/15/20066/16/20066/16/2006 10:15:24 AMAPASS
Life safety inspection is satisfactory.
BLD05-00313 FIRE-Final Inspection6/15/20066/16/20066/16/2006 9:28:21 AMAPASS
Items on correction notice have been verified for completion, life safety inspection passed.
FIR05-00764 INSP-Final Inspection6/15/20066/16/20066/16/2006 9:07:21 AMACANC
Per phone call from contractor, inspection to be rescheduled due to jobsite conditions.
MIS06-00091 FIR-Final6/15/20066/16/20066/16/2006 9:05:35 AMAPASS
Corrections have been completed, inspection passed. NOTE: No sign off card available on site at the time of inspection.
FIR06-00159 INSP-Final Inspection6/15/20066/16/20066/15/2006 1:40:09 PMACANC
Forrest, We would like to reschedule this for late AM if at all possible. Please let us know as soon as possible when you can make it. ###-####. Thanks, Jason; Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick
FIR06-00321 INSP-Sprinkler Rough-in/Hydro6/14/20066/16/20066/15/2006 8:50:42 AMACANC
Contact Dave UG Cover Inspection; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley