Inspections for the day of: Monday, June 16, 2008.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00320 INSP-Final Inspection6/16/20086/16/20086/16/2008 5:31:45 PMPNR
Jim Phone #: ###-####
FIR08-00258 INSP-Final Inspection6/16/20086/16/20086/16/2008 5:31:20 PMPPASS
Scope of demo permit work is complete.
FIR07-00854 INSP-Final Inspection6/16/20086/16/20086/16/2008 5:29:51 PMAPASS
UG fire supply line permit finaled.
BLD08-00947 FIRE-Final Inspection6/16/20086/16/20086/16/2008 5:27:06 PMPPASS
Fire life safety finaled.
FIR07-00086 INSP-Sprinkler Rough-in/Hydro6/16/20086/16/20086/16/2008 5:26:37 PMPPART
See approved plans for areas good for cover at hard lid and drop ceilings.
FIR08-00420 INSP-Final Inspection6/13/20086/16/20086/16/2008 12:26:39 PMPFAIL
Noted wall mounted notification appliances at six locations are below the min. height AFF per NFPA 72-see fire code review notes item #20, one ceiling mounted a/v needs to be installed per plan, remainder of installation appears acceptable however no functional testing performed due to devices to be relocated/adjusted.
FIR08-00195 FIR-Aging Inspection6/16/20086/16/20086/16/2008 12:20:43 PM DEFR
Need final inspection request for work completed.
FIR07-00897 INSP-Final Inspection6/16/20086/16/20086/16/2008 12:19:31 PMAPASS
UG fire supply line permit finaled, hydrostatic testing completed in conjunction with overhead hydrostatic tests done on 1/29/08 per documented activity under OH permit FIR07-00997.
BLD07-01654 BLD-Conference6/16/20086/16/20086/16/2008 12:14:08 PMADONE
Jim Phone #: ###-####
FIR08-00117 INSP-Final Inspection6/16/20086/16/20086/16/2008 12:13:47 PMAPART
Final pending repair of the non-functional outside waterflow bell.
FIR08-00361 INSP-Sprinkler Rough-in6/16/20086/16/20086/16/2008 12:12:41 PMAPART
OH rough-in okayed for cover as indicated for units one, two and three, first and second floors.
FIR08-00420 INSP-Final Inspection6/13/20086/16/20086/13/2008 4:08:55 PMACANC
Phone #: ###-#### Internet Inspection Request from: Diane Turner Inspection cancelled from web by: Diane Turner